Post on 04-Aug-2020
LPS series and CB series
Centralised systems for emergency lighting
www. d a i s a l u x . c o m / 9 0 2 2 0 8 1 0 8
Table of Contents
Operation and specifications 4
Wiring diagrams 6
Reference and specifications table 7
Order forms 8
Accessories 9
Monitoring unit 10
DaisaTest System 22
Luminaires for centralised units 24
Pages
4 to 11
LPS
3
Operation and specifications 12
Wiring diagrams 14
Reference and specifications table 15
Order forms 16
Accessories 19
Monitoring unit 20
DaisaTest System 22
Luminaires for centralised units 24
Pages
12 to 21
CB
4
• Maximum output power 300 W·(up to 3 hours duration).
• Power factor: 0.98 when fully charged.
• 4 A output circuit with double terminal, maintained/non-maintained configuration and fuse-free dynamic short-circuit protection.
• Option of installing Daisalux beacons with dimming.
• The DBR system can also be installed in ELC-type luminaires.
• Sealed valve-regulated lead-acid battery (VRLA).
• High rate battery charge.
• Top-mounted power supply intakes and outlets.
• Control panel with graphic display and keyboard for configuration and monitoring of the central battery.
• Front-loading mini-USB for PC connection.
• Ethernet connection with PC (LPSLan accessory) or web server for DaisaTest system.
• Integration with DaisaTest system for maintenance management (EN-50172).
•Inputs:• 4 digital inputs (detector connection)
• 1 analogue input (1-10 V) for regulating Daisalux beacons
• 1 Daisalux remote control input.
•Alarms: • 4 dry contacts for failures, alarms and central battery status (EN-50171).
LPSSeries
Centralised units|Operationandspecifications
The LPS Series centralised units are designed and constructed in accordance with the EN 50171 standard for uninterruptible-type emergency lighting. They are low-power centralised wall-mounted units with an output voltage of 24 Vdc.
Cable inletand outlet Connection terminal block
Rectifierand circuitboard
Pb VRLA batteries
Control panel
Fuses for batteries
Ventilation
Wallmounting bracket
Internal operation diagram
6 Centralised units|Wiringdiagrams
Connectionterminalblock
Power sourceRemote control Auxiliary inputs
Dry contacts 0-10 V beacon lighting regulation
Outputs
Each LPS unit output circuit is configured as "maintained / non-maintained”. This operating mode is assigned to all non-electric line communication (non-ELC) luminaires connected to said circuit.
If luminaires with electric line communication (ELC) are used, the "maintained / non-maintained" operating mode is individually configured on each luminaire and is independent of the circuit configuration.
The DaisaTest application (through the LPSLan communication accessory) can monitor and control an indefinite number of devices.
Ethernet (LPSLan) or USB LPSLan via web
6 outputcircuits
Maximum: 4 A per circuit
6 outputcircuits
Maximum: 4 A per circuit
Option ofmultiple units
6 outputcircuits
Maximum: 4 A per circuit
Power supply input
LPSSeries
7Referenceandspecificationstable|Centralised units
LPS24-26 LPS24-65
Inputs 230V 110-127V 230V 110-127VPower source voltage 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Maximum cable duct diameter 2.5 mm2
Input protection 6.3 AT fuse
Analogue (Daisalux beacon regulation) 1 (0-10 Vdc)Auxiliary inputs 4Remote control 1
OutputsOutput voltage: 24 Vdc (21.6 V - 30 V)
Maximum output cable diameter 2.5 mm2
Maximum output power Duration 0.5 h 300 W 200 W 300 W 200 W 1 h 300 W 200 W 300 W 200 W 1.5 h 211 W 200 W 300 W 200 W 2 h 170 W 170 W 300 W 200 W 3 h 124 W 124 W 300 W 200 W 6 h 69 W 69 W 172 W 172 W 8 h 55 W 55 W 136 W 136 WNo. of output circuits 6
Overcurrent protection 4.1 A Overvoltage 34V Short circuit 12-24 A constant until thermal protection Self-reset (detection< 20 s) Overheating 80 ºC self-reset (detection < 20 s)Dry contacts 4 (3 fixed under EN 50171)
InteractionandconnectivityUSB Central battery front-mounted connection
Ethernet or Wifi Optional with LPSLan accessoryDisplay 160x104-dot graphic display
with central battery front-mounted keyboard
GeneralProtection class Class IDegree of protection IP20Ambient working temperature between 0 and 25 ºCNoise level < 40 dBWeight: 27 kg 56 kgBattery 24V / 26Ah Pb VRLA 24V / 65Ah Pb VRLA
SoftwareWinCBS Yes
Soft-DaisaTest Optional with ELC unit and luminaires
8 Centralised units|Orderform
Orderform
Model Dimensions Battery Durationinhours(configurable)
LPS24-26 405x400x225 24V - 26 Ah 0.5 / 1 / 1.5 / 2 / 3 / 6 / 8
LPS24-65 605x400x225 24 V - 65 Ah 0.5 / 1 / 1.5 / 2 / 3 / 6 / 8
LPS24-26
Finishes
Finish Description Marking
Voltage 220-230V 50/60 Hz ---- voltage 110-127V 50/60 Hz (110-127V)
Reference Description
LPSLan Communication module Ethernet and Wifi.
DR-3 Remote three-phase/single-phase network fault detector.
Accessories
LPSSeries40
0
405
400
225 16
LPS24-65
400
225 16
600
605
9Accessory|Centralised units
Web server
Communication modulesLPSLan communication module.Communication module via Ethernet connection with integrated web server.Enables monitoring of the central battery and ELC-type luminaires.
DR-3remotedetector.
Network fault detector for centralised LPS series units.
Monitors the status of the network (3 phases and neutral) which it shows by flashing a front-mounted LED (off during network downtime).
It has two contacts (NO, NC) connected to the LPS central battery auxiliary inputs and, in the event of a network fault, enables configuration of the output circuit start command.
54
45
44
50
83
35
10 Centralised units|Monitoringunit
The monitoring unit controls the most critical aspects of safety (EN-50171) of the LPS units such as the status of the battery-charging rectifier, the general condition of the central battery, the status of the output circuits and runs functional, duration and battery capacity tests.
It controls the charge voltage and current of the batteries and their temperature.
General status synoptic display
A control panel with graphic LCD display enables data monitoring and performs the following configuration tasks:
• Definition of the central battery’s duration.
• Configuration of the circuits in maintained / non-maintained mode.
• Configuration of the frequency of the tests, day of the week,
test schedule, automatic/manual mode.
• Input configuration.
• Output circuit configuration.
• Display of scenarios programmed with winCBS or web server.
• Zoning of communicating luminaires (ELC)
• Operational configuration of ELC-type luminaires (maintained/non-maintained)
• Display of ELC-type luminaire status.
• Internal memory with central battery configuration log, test results and status of ELC-type luminaires.
LPSSeries
11Monitoringunit|Centralised unit
Menuwindows
General condition of the central battery, batteries, rectifier and fault alarms
Configuration of functional, duration and battery capacity tests
Configuration of the inputs, output alarms, duration and web server.
Execution of actions and scenarios
General system information
Monitoring and configuration of communicating ELC circuits and luminaires.
Menu
System Test Config Outputs Actions Info
SistemaSystem Test
Config
#
Acciones
Salidas
Info
Test
Config
Actions
Outputs
Info
CBSeries
• Maximum of 20 output circuits in CB800 and CB1250 units, 40 circuits in CB2500 and 60 circuits in CB5000.
• Option of configuring different autonomies for each output circuit.
• Sealed valve-regulated lead-acid battery (VRLA).
• High rate battery charge.• Top-mounted power supply intakes and outlets.
• Control panel for configuration and monitoring of the central battery.
• Front-loading mini-USB for PC connection.
• Ethernet connection with PC for DaisaTest System.
• Integration with DaisaTest system for maintenance management (EN-50172).
• The DBR system can also be installed in ELC-type luminaires.
Inputs:• 2 auxiliary inputs for remote actions.
• Communication port for EV-BUS.
• 1 x 230 V output for installation of EV-ALIM bus power source.
•Alarms: • 5 dry contacts for faults, alarms and central battery status (EN-50171).
The CB series centralised units for emergency lighting in switched mode or without breaker are designed and built in accordance with EN 50171. It is a centralised unit with 230 Vac / 24 Vdc output voltages and a maximum power output of 800 VA, 1250 VA, 2500 VA and 5000 VA. (Contact Daisalux for information about other outputs).
Power supply input and outputs
Distribution sub-rack
Rectifier(ac / dc)
Distribution cards
Pb VRLAbatteries
Ventilation
Monitoringunit
Invertor(dc / ac)
Electrical protection
Internal operation diagram
12 Centralised units|Operationandspecifications
CBSeries
Connectionterminalblock
Each CB unit output circuit is configured as "maintained / non-maintained" and assign this operating mode to all luminaires without communication (non-ELC) connected to said circuits.
If the unit and luminaires are communicated (ELC), "maintained / non-maintained" operation is individually configured in each luminaire and is independent of the circuit configuration.
The DaisaTest application can monitor and control an indefinite number of units. No communication accessory is required.
CB800/1250 outputs
Power supply input
Dry contacts
Ethernet or USB
Up to20 outputcircuits
Up to 20 outputcircuits
Up to 40 outputcircuits
Up to 60 outputcircuits
Power supply input
CB800 CB1250 CB2500 CB5000
14 Centralised units |Wiringdiagrams
CB800 CB1250 CB2500 CB5000
Inputs Power source voltage 230V 50/60 Hz 230/400V 50/60 HzMaximum cable duct diameter 2.5 mm2 4 mm2 4x4 mm2
Input protection 10 A 16 A 4x20 AAuxiliary inputs 2BUS-EV 1
OutputsOutput voltage 230V 50 Hz / 230V 60 HzMaximum output cable diameter 2.5 mm2
Maximum output power 800 VA 1250 VA 2500 VA 5000 VANo. of distribution sub-racks 1 1 or 2 2 or 3No. of cards per sub-rack 10
Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A
No. of output circuits up to 20 up to 40 up to 60
Output protection (fuse) 230 Vac 2 A 4 A 4 A 6.3 A 6.3 A 24 Vdc 4 A 6.3 AIsolation detector (IT) Non-interruptible and emergency modeDry contacts 5 (3 fixed under EN 50171)
InteractionandconnectivityUSB Central Battery front-mounted connectionEthernet Connection on the distribution terminal blockDisplay 160x104-dot graphic display
with central battery front-mounted keyboardSD board central battery front-mounted
GeneralProtection class Class IDegree of protection IP20Ambient working temperature between 0 and 25 ºC 24 V from 55 Ah 24 V from 75 Ah up to 150 Ah up to 150 Ah Batteries (depending on power and 24V - 200Ah with 24V from 200Ah 24V from 90Ah 24V from 250Ah required duration) additional cabinet up to 250 Ah with up to 2x250 Ah up to 4x250 Ah of batteries additional cabinet of batteries No. of rectifications 1 2 3 to 6Redundancy OptionalInvertor 1000 VA 1500 VA 3000 VA 2x3000 VAKey 5 mm double bitted (other types of key optional)
AccessoriesEV-DRY YesEV-PD YesEV-ALIM Yes
SoftwareWinCBS YesSoft-DaisaTest Optional with ELC unit and luminaires
15Referenceandspecificationstable|Centralised units
16 Centralised units| Orderform
OrderformCB800
Reference Description
EV-DR Remote three phase/single phase network fault detector
EV-PD Level detector.
EV-ALIM bus power source.
Accessories
CB800-1-1- - - - - -
selectoption
Capacityof thebattery
in Ah (24V)
55657590100150200
90 Ah 1 h 150 Ah 2 h 200 Ah 3 h
selectoption
Conventionalor
communicating
---- (of series)ELC
(From0to10)
Numberof outputboards2x230Vac
(From0to10)
Number of output boards 1x230V
ac
The total number of distribution cards(sum of the four columns)
may not exceed 10.
(From0to10)
Numberof outputboards2x24Vdc
Estimation of batteries based on
duration
(From0to10)
Numberof outputboards1x24Vdc
With batteries up to 150 Ah
1935
600
400
CB800
With additional battery cabinet (200 Ah)
CBSeries
600
400
1335
17Orderform|Centralised units
OrderformCB1250
Reference Description
EV-DR Remote three phase/single phase network failure detector
EV-PD Level detector.
EV-ALIM Bus power source.
Accessories
CB1250-1-1- - - - - -
selectoption
Capacityof thebattery
in Ah (24V)
7590100150200250
100 Ah 1 h 200 Ah 2 h 250 Ah 3 h
selectoption
Conventionalor
communicating
---- (of series)ELC
(From0to10)
Number of output boards 2x230V
ac
(From0to10)
Number of output boards 1x230V
ac
The total number of distribution cards(sum of the four columns)
may not exceed 10.
(From0to10)
Number of output boards 2x24Vdc
Estimation of batteries based on
duration
(From0to10)
Number of output boards 1x24Vdc
With batteries up to 150 Ah
CB1250
With additional battery cabinet (200 and 250 Ah)
600
400
1335
1935
600
400
18 Centralised unit|Examplesoforder
OrderformCB2500
CB2500-1-2- - - - - -selectoption
Capacity of the battery
in Ah (24V)
901001502002502x1502x2002x250 200 Ah 1 h
2x200 Ah 2 h 2x250 Ah 3 h
selectoption
Conventionalor
communicating
---- (of series)ELC
(From0to20)
Number of output boards 2x230V
ac
(From0to20)
Numberof outputboards1x230Vac
The total number of distribution cards(sum of the four columns)
may not exceed 20.
(From0to20)
Number of output boards 2x24Vdc
Estimation of batteries based on
duration
(From0to20)
Number of output boards 1x24Vdc
CB5000
Reference Description
EV-DR Remote three phase/single phase network fault detector
EV-PD Level detector.
EV-ALIM Bus power source.
Accessories
Orderform
Reference Description
EV-DR Remote three phase/single phase network fault detector
EV-PD Level detector.
EV-ALIM Bus power source.
Accessories
CB5000-3-3- - - - - -
4x150 Ah 1 h 4x200 Ah 2 h 4x250 Ah 3 h
(From0to30)
Number of output boards 2x230 V
ac
(From0to30)
Number of output boards 1x230V
ac
The total number of distribution cards(sum of the four columns)
may not exceed 30.
(From0to30)
Number of output boards 2x24Vdc
Estimation of batteries based on
duration
(From0to30)
Number of output boards1x24 Vdc
selectoption
Capacityof thebattery
in Ah (24V)
2502x1502x2002x250 4x1504x2004x250
selectoption
Conventionalor
communicating
---- (of series)ELC
CBSeries13
35
1200
400
2135
1200
600
RemoteEV-DRnetwork faultdetector• Network fault detector for CB
series centralised unit.• Monitors the status of the
network (3 phases and neutral) which it shows by flashing a front-mounted LED (off during network downtime).
• In the event of a network failure it sends a signal via the EV bus to the CB unit which enables configuration of the command to activate one or more output circuits.
• Sending signal to centralised unit via EV bus.
Leveldetector EV-PD• Level detector for CB series
centralised unit.• It has two monitoring inputs
(1-2 and 2-3) that enable configuration of activation order of one or more central battery output circuits.
• Sending signal to centralised unit via EV bus.
Buspowersource EV-ALIM• Power source for EV devices
connected to centralised CB series unit.
• It supplies the devices connected to the unit through the EV bus itself.
• The number of devices supplied depends on their distance from the power source.
• The capacity is a maximum of 10 devices at a distance of 400 m.
19Accessory|Centralised units
Accessoryconnection
90
71
1870
83
54
45
44
50
54
45
44
50
83
35
20 Centralised units|Monitoringunit
The monitoring unit controls the most critical aspects of safety (EN-50171) of the CB units such as the status of
the battery-charging rectifier, the general condition of the central battery, the status of the inverter, status of
the output circuits and runs functional, duration and battery capacity tests.
It controls the charge voltage and current of the batteries
and their temperature.
A control panel with graphic LCD display enables data monitoring and performs the following configuration tasks:
• Definition of the general duration of the central battery or output circuits.
• Configuration of the output circuits as maintained / non-maintained and ELC luminaires.
• Configuration of the frequency of the tests, day of the week, test schedule, automatic/manual mode.
• Input configuration.
• Output configuration.
• Configuration of EV-DR and EV-PD detectors.
• SD card with central battery configuration log, test results and status of the ELC-type luminaires.
Generalstatussynopticdisplay
CBSeries
21Monitoringunit|Centralised unit
Menuwindows
Status general of the central battery, batteries, rectifier and fault alarms
Configuration of functional, duration and battery capacity tests
Central battery configuration, dry contacts and Aux in
Execution of actions General system information
Output circuit and communicating luminaire configuration
Menu
System Test Config Devices Actions Info
SistemaSystem Test
Config
#
Acciones
Salidas
Info
Test
Config
Actions
Devices
Info
22 Centralised unit|DaisaTestSystem
DaisaTestSystemA Daisatest System is a
type of emergency lighting installation capable of monitoring the status of each centralised unit and
emergency luminaire.
The system is compatible with installations due to the use of autonomous luminaires and centralised systems. It is
capable of including the two integrated systems in the same software in a single
installation.
The communication technology for centralised systems
is known as ELC (electric line communication) and
does not require a specific communication cable. The
central battery's own power cable to the luminaires also
carries the communication signal between the emergency luminaires and the system.
Based on the EN 50172 and EN 62034 (IEC 62034) standards,
the system constantly monitors and supervises the status of the installation. It runs regular operating
and duration tests on the centralised unit and
luminaires.
It makes maintenance proposals based on criteria previously set by the user.
Building and plant plan
window.A logical
plans browsing menu makes
identification of the status of the luminaires and units easy
to access.
General window of the installation.
Communication tree window. It provides
identification of the system
wiring and communication
structure.
DaisaTestSoftware
Note:
Both the central battery and the luminaires must be ELC if CB series central batteries units are used with DaisaTest System.When LPS series central batteries are used, the LPSLan accessory and the emergency luminaires that must be ELC must be selected together with the central batteries.
23DaisaTestsystem|Centralised unit
Central battery specs sheet window.
Luminaire specs sheet window.Luminous flux regulation option (dimming) of luminaires and activation of the luminosity sensor (eco-permanence) configured as maintained.
24 Centralised unit|Luminairesforcentralisedunits
Luminaires
S lens ESP lens ES lens HydraIzar
Myra GaliaNorma Iris Sol
Hydra-G NovaArgos-MArgos-DArgus
Orto Galia-B Galia-AD Orto-SGalia-S
AD lens EST lensBlock R lens C lens
Luminairesforcentralisedunit|Centralised units 25
Vir 160x160Vir 210x210Vir 320x195Ikus 220x220
Carril Flame-proof Zenit Zenit EstancoZenit PL
Lisu
Ikus
AquaLecuAlzir-InoxAlzir Lyra
Leda Clavo
Beaconlighting
All the models that appear in this catalogue have been created and patented by Daisalux SAU and are for the exclusive use of this company.Daisalux reserves the right to amend the information in this catalogue without prior notice.
DOC-CENTRAL-EN / Version 1 – Review 1 - 15/04/2018