MODEL

PEFY-W-VMS-APEFY-W-VMA(L)-APEFY-W-VMA2-APFFY-W-VCM-A

PUHY-M-YNW-A1 (-BS)PUHY-EM-YNW-A1 (-BS)

PEFY-WP-VMS1-EPEFY-W-VMS-APEFY-WP-VMA-EPEFY-W-VMA(L)-APEFY-W-VMA2-APLFY-WP-VFM-EPLFY-WP-VBM-EPFFY-WP-VLRMM-EPFFY-W-VCM-A

PURY-M-YNW-A1 (-BS)PURY-EM-YNW-A1 (-BS)

AIR CONDITIONING SYSTEMS

HYBRID CITY MULTI

MEES18K071

CAPACITY TABLES

Heat Pump Y-Series ...................................................................................................................................1

Heat Recovery R2-Series ...........................................................................................................................9

MEES18K071_TOC_CAPACITY.fm 1 ページ 2019年3月1日 金曜日 午前9時25分

MEES18K071

MEES18K071_TOC_CAPACITY.fm 2 ページ 2019年3月1日 金曜日 午前9時25分

Capacity Tables

MEES18K106 9

CONTENTS CAPACITY TABLES

I.CAPACITY TABLES

1. [Ceiling concealed (Low static pressure type)] ......................................................................................... 10

1-1. Cooling capacity with PURY-(E)M200-250YNW-A1........................................................................ 101-2. Cooling capacity with PURY-(E)M300-350YNW-A1........................................................................ 101-3. Cooling capacity with PURY-(E)M400-500YNW-A1........................................................................ 11

2. [Ceiling concealed (Medium static pressure type)] ................................................................................... 12

2-1. Cooling capacity with PURY-(E)M200-250YNW-A1........................................................................ 122-2. Cooling capacity with PURY-(E)M300-350YNW-A1........................................................................ 122-3. Cooling capacity with PURY-(E)M400-500YNW-A1........................................................................ 13

3. [Ceiling cassette (4-way flow type)] .......................................................................................................... 15

3-1. Cooling capacity with PURY-(E)M200-250YNW-A1........................................................................ 153-2. Cooling capacity with PURY-(E)M300-350YNW-A1........................................................................ 153-3. Cooling capacity with PURY-(E)M400-500YNW-A1........................................................................ 15

4. [Floor standing (Concealed type)]............................................................................................................. 16

4-1. Cooling capacity with PURY-(E)M200-250YNW-A1........................................................................ 164-2. Cooling capacity with PURY-(E)M300-350YNW-A1........................................................................ 164-3. Cooling capacity with PURY-(E)M400-500YNW-A1........................................................................ 16

5. [All indoor units] ........................................................................................................................................ 18

5-1. Heating capacity with PURY-(E)M200-250YNW-A1........................................................................ 185-2. Heating capacity with PURY-(E)M300-350YNW-A1........................................................................ 185-3. Heating capacity with PURY-(E)M400-500YNW-A1........................................................................ 185-4. Heating capacity with PURY-(E)M200-250YNW-A1 "COP priority mode"....................................... 195-5. Heating capacity with PURY-(E)M300-350YNW-A1 "COP priority mode"....................................... 195-6. Heating capacity with PURY-(E)M400-500YNW-A1 "COP priority mode"....................................... 19

0000005141.BOOK 9 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

10

1. [Ceiling concealed (Low static pressure type)] CAPACITY TABLES

I.CAPACITY TABLES1. [Ceiling concealed (Low static pressure type)]1-1. Cooling capacity with PURY-(E)M200-250YNW-A1

1-2. Cooling capacity with PURY-(E)M300-350YNW-A1

PEFY-WP-VMS1-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.5 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.6 1.9 1.6

20 (2.2) 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.7 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.9 3.9 2.8 4.1 2.8

40 (4.5) 4.0 3.2 4.1 3.3 4.4 3.3 4.5 3.5 4.6 3.5 4.9 3.4 5.2 3.4

50 (5.6) 5.0 4.0 5.2 4.2 5.5 4.1 5.6 4.4 5.8 4.4 6.0 4.3 6.4 4.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.5 4.1 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.9 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-WP-VMS1-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.5 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.6 1.9 1.6

20 (2.2) 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.7 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.9 3.9 2.8 4.1 2.8

40 (4.5) 4.0 3.2 4.1 3.3 4.4 3.3 4.5 3.5 4.6 3.5 4.9 3.4 5.2 3.4

50 (5.6) 5.0 4.0 5.2 4.2 5.5 4.1 5.6 4.4 5.8 4.4 6.0 4.3 6.4 4.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.5 4.1 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.9 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 10 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

11

1. [Ceiling concealed (Low static pressure type)] CAPACITY TABLES

1-3. Cooling capacity with PURY-(E)M400-500YNW-A1

PEFY-WP-VMS1-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 0.9 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.5 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.6

20 (2.2) 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.0 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.6 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.9 3.9 2.8 4.2 2.8

40 (4.5) 4.0 3.2 4.1 3.3 4.3 3.3 4.5 3.5 4.6 3.5 4.9 3.4 5.2 3.4

50 (5.6) 5.0 4.0 5.1 4.1 5.4 4.1 5.6 4.4 5.7 4.4 6.1 4.3 6.5 4.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 0.9 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.3 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.1 3.9 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 11 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

12

2. [Ceiling concealed (Medium static pressure type)] CAPACITY TABLES

2. [Ceiling concealed (Medium static pressure type)]2-1. Cooling capacity with PURY-(E)M200-250YNW-A1

2-2. Cooling capacity with PURY-(E)M300-350YNW-A1

PEFY-WP-VMA-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.6 2.8 2.8 2.9 2.7 3.0 2.7 3.2 2.7

32 (3.6) 3.2 3.0 3.3 3.1 3.5 3.1 3.6 3.3 3.7 3.3 3.9 3.3 4.1 3.2

40 (4.5) 4.0 3.8 4.1 3.9 4.4 3.9 4.5 4.2 4.6 4.1 4.9 4.1 5.2 4.0

50 (5.6) 5.0 4.2 5.2 4.3 5.5 4.3 5.6 4.6 5.8 4.6 6.0 4.5 6.4 4.4

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.5 7.7 5.4 8.1 5.3

71 (8.0) 7.2 6.8 7.4 7.1 7.8 7.0 8.0 7.6 8.2 7.5 8.6 7.4 9.2 7.3

80 (9.0) 8.1 7.2 8.3 7.5 8.8 7.4 9.0 7.9 9.3 7.9 9.7 7.8 10.3 7.7

100 (11.2) 10.0 8.1 10.3 8.4 10.9 8.3 11.2 8.8 11.5 8.8 12.1 8.6 12.8 8.5

125 (14.0) 12.5 10.1 12.9 10.4 13.7 10.3 14.0 10.9 14.4 10.9 15.1 10.7 16.0 10.5

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.2 4.6 5.5 4.5 5.6 4.9 5.8 4.8 6.0 4.8 6.4 4.7

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.4 7.7 5.3 8.1 5.3

71 (8.0) 7.2 5.4 7.4 5.6 7.8 5.5 8.0 5.9 8.2 5.8 8.6 5.7 9.2 5.6

80 (9.0) 8.1 5.9 8.3 6.0 8.8 6.0 9.0 6.3 9.3 6.2 9.7 6.1 10.3 6.0

100 (11.2) 10.0 8.0 10.3 8.3 10.9 8.2 11.2 8.7 11.5 8.6 12.1 8.5 12.8 8.4

125 (14.0) 12.5 9.7 12.9 10.0 13.7 9.8 14.0 10.4 14.4 10.4 15.1 10.2 16.0 10.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.1 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.4 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.2 5.2 5.5 5.5 5.6 5.6 5.8 5.8 6.0 6.0 6.4 6.4

63 (7.1) 6.4 6.4 6.5 6.5 6.9 6.9 7.1 7.1 7.3 7.3 7.7 7.7 8.1 8.1

71 (8.0) 7.2 7.2 7.4 7.4 7.8 7.8 8.0 8.0 8.2 8.2 8.6 8.6 9.2 8.5

80 (9.0) 8.1 8.1 8.3 8.3 8.8 8.5 9.0 9.0 9.3 9.1 9.7 9.0 10.3 8.9

100 (11.2) 10.0 9.1 10.3 9.4 10.9 9.3 11.2 10.0 11.5 9.9 12.1 9.8 12.8 9.6

125 (14.0) 12.5 10.2 12.9 10.6 13.7 10.4 14.0 11.1 14.4 11.0 15.1 10.8 16.0 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-WP-VMA-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.6 2.8 2.8 2.9 2.7 3.0 2.7 3.2 2.7

32 (3.6) 3.2 3.0 3.3 3.1 3.5 3.1 3.6 3.3 3.7 3.3 3.9 3.3 4.1 3.2

40 (4.5) 4.0 3.8 4.1 3.9 4.4 3.9 4.5 4.2 4.6 4.1 4.9 4.1 5.2 4.0

50 (5.6) 5.0 4.2 5.2 4.3 5.5 4.3 5.6 4.6 5.8 4.6 6.0 4.5 6.4 4.4

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.5 7.7 5.4 8.1 5.3

71 (8.0) 7.2 6.8 7.4 7.1 7.8 7.0 8.0 7.6 8.2 7.5 8.6 7.4 9.2 7.3

80 (9.0) 8.1 7.2 8.3 7.5 8.8 7.4 9.0 7.9 9.3 7.9 9.7 7.8 10.3 7.7

100 (11.2) 10.0 8.1 10.3 8.4 10.9 8.3 11.2 8.8 11.5 8.8 12.1 8.6 12.8 8.5

125 (14.0) 12.5 10.1 12.9 10.4 13.7 10.3 14.0 10.9 14.4 10.9 15.1 10.7 16.0 10.5

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 12 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

13

2. [Ceiling concealed (Medium static pressure type)] CAPACITY TABLES

2-3. Cooling capacity with PURY-(E)M400-500YNW-A1

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.2 4.6 5.5 4.5 5.6 4.9 5.8 4.8 6.0 4.8 6.4 4.7

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.4 7.7 5.3 8.1 5.3

71 (8.0) 7.2 5.4 7.4 5.6 7.8 5.5 8.0 5.9 8.2 5.8 8.6 5.7 9.2 5.6

80 (9.0) 8.1 5.9 8.3 6.0 8.8 6.0 9.0 6.3 9.3 6.2 9.7 6.1 10.3 6.0

100 (11.2) 10.0 8.0 10.3 8.3 10.9 8.2 11.2 8.7 11.5 8.6 12.1 8.5 12.8 8.4

125 (14.0) 12.5 9.7 12.9 10.0 13.7 9.8 14.0 10.4 14.4 10.4 15.1 10.2 16.0 10.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.1 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.4 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.2 5.2 5.5 5.5 5.6 5.6 5.8 5.8 6.0 6.0 6.4 6.4

63 (7.1) 6.4 6.4 6.5 6.5 6.9 6.9 7.1 7.1 7.3 7.3 7.7 7.7 8.1 8.1

71 (8.0) 7.2 7.2 7.4 7.4 7.8 7.8 8.0 8.0 8.2 8.2 8.6 8.6 9.2 8.5

80 (9.0) 8.1 8.1 8.3 8.3 8.8 8.5 9.0 9.0 9.3 9.1 9.7 9.0 10.3 8.9

100 (11.2) 10.0 9.1 10.3 9.4 10.9 9.3 11.2 10.0 11.5 9.9 12.1 9.8 12.8 9.6

125 (14.0) 12.5 10.2 12.9 10.6 13.7 10.4 14.0 11.1 14.4 11.0 15.1 10.8 16.0 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-WP-VMA-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.8 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.5 2.5 2.5 2.7 2.5 2.8 2.8 2.9 2.7 3.0 2.7 3.2 2.7

32 (3.6) 3.2 3.0 3.3 3.1 3.5 3.1 3.6 3.3 3.7 3.3 3.9 3.3 4.2 3.2

40 (4.5) 4.0 3.7 4.1 3.9 4.3 3.8 4.5 4.2 4.6 4.1 4.9 4.1 5.2 4.0

50 (5.6) 5.0 4.2 5.1 4.3 5.4 4.3 5.6 4.6 5.7 4.5 6.1 4.5 6.5 4.4

63 (7.1) 6.3 5.1 6.4 5.2 6.8 5.1 7.1 5.5 7.3 5.5 7.7 5.4 8.2 5.3

71 (8.0) 7.1 6.8 7.2 7.0 7.7 7.0 8.0 7.6 8.2 7.5 8.7 7.4 9.2 7.3

80 (9.0) 8.0 7.2 8.1 7.4 8.7 7.4 9.0 7.9 9.2 7.9 9.8 7.8 10.4 7.7

100 (11.2) 10.0 8.1 10.1 8.3 10.8 8.2 11.2 8.8 11.5 8.8 12.2 8.6 12.9 8.5

125 (14.0) 12.5 10.0 12.7 10.3 13.5 10.2 14.0 10.9 14.4 10.8 15.2 10.7 16.1 10.6

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.5 1.9

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.1 4.6 5.4 4.5 5.6 4.9 5.7 4.8 6.1 4.8 6.5 4.7

63 (7.1) 6.3 5.0 6.4 5.2 6.8 5.1 7.1 5.5 7.3 5.4 7.7 5.4 8.2 5.3

71 (8.0) 7.1 5.4 7.2 5.5 7.7 5.5 8.0 5.9 8.2 5.8 8.7 5.7 9.2 5.6

80 (9.0) 8.0 5.9 8.1 6.0 8.7 5.9 9.0 6.3 9.2 6.2 9.8 6.2 10.4 6.1

100 (11.2) 10.0 8.0 10.1 8.2 10.8 8.1 11.2 8.7 11.5 8.6 12.2 8.5 12.9 8.4

125 (14.0) 12.5 9.6 12.7 9.9 13.5 9.8 14.0 10.4 14.4 10.4 15.2 10.2 16.1 10.1

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 13 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

14

2. [Ceiling concealed (Medium static pressure type)] CAPACITY TABLES

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.5 2.5 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.2 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.3 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.1 5.1 5.4 5.4 5.6 5.6 5.7 5.7 6.1 6.1 6.5 6.5

63 (7.1) 6.3 6.3 6.4 6.4 6.8 6.8 7.1 7.1 7.3 7.3 7.7 7.7 8.2 8.2

71 (8.0) 7.1 7.1 7.2 7.2 7.7 7.7 8.0 8.0 8.2 8.2 8.7 8.6 9.2 8.5

80 (9.0) 8.0 8.0 8.1 8.1 8.7 8.4 9.0 9.0 9.2 9.1 9.8 9.0 10.4 8.9

100 (11.2) 10.0 9.0 10.1 9.3 10.8 9.3 11.2 10.0 11.5 9.9 12.2 9.8 12.9 9.7

125 (14.0) 12.5 10.2 12.7 10.4 13.5 10.4 14.0 11.1 14.4 11.0 15.2 10.9 16.1 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 14 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

15

3. [Ceiling cassette (4-way flow type)] CAPACITY TABLES

3. [Ceiling cassette (4-way flow type)]3-1. Cooling capacity with PURY-(E)M200-250YNW-A1

3-2. Cooling capacity with PURY-(E)M300-350YNW-A1

3-3. Cooling capacity with PURY-(E)M400-500YNW-A1

PLFY-WP-VFM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.1 1.2 1.1 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.3 1.6 1.3 1.7 1.3 1.7 1.4 1.7 1.4 1.8 1.3 1.9 1.3

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.5 1.7

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.0 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.6 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.8 3.9 2.8 4.1 2.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PLFY-WP-VBM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.3 3.6 3.5 3.7 3.5 3.9 3.5 4.1 3.4

40 (4.5) 4.0 3.6 4.1 3.7 4.4 3.6 4.5 3.9 4.6 3.9 4.9 3.8 5.2 3.8

50 (5.6) 5.0 4.2 5.2 4.4 5.5 4.3 5.6 4.6 5.8 4.6 6.0 4.5 6.4 4.4

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PLFY-WP-VFM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.1 1.2 1.1 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.3 1.6 1.3 1.7 1.3 1.7 1.4 1.7 1.4 1.8 1.3 1.9 1.3

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.5 1.7

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.0 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.6 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.8 3.9 2.8 4.1 2.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PLFY-WP-VBM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.3 3.6 3.5 3.7 3.5 3.9 3.5 4.1 3.4

40 (4.5) 4.0 3.6 4.1 3.7 4.4 3.6 4.5 3.9 4.6 3.9 4.9 3.8 5.2 3.8

50 (5.6) 5.0 4.2 5.2 4.4 5.5 4.3 5.6 4.6 5.8 4.6 6.0 4.5 6.4 4.4

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PLFY-WP-VFM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.1 1.2 1.1 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.3 1.5 1.3 1.6 1.3 1.7 1.4 1.7 1.4 1.9 1.3 2.0 1.3

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7

25 (2.8) 2.5 2.0 2.5 2.0 2.7 2.0 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.6 3.3 2.7 3.5 2.7 3.6 2.9 3.7 2.8 3.9 2.8 4.2 2.8

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PLFY-WP-VBM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.3 3.6 3.5 3.7 3.5 3.9 3.5 4.2 3.4

40 (4.5) 4.0 3.5 4.1 3.7 4.3 3.6 4.5 3.9 4.6 3.9 4.9 3.8 5.2 3.8

50 (5.6) 5.0 4.2 5.1 4.3 5.4 4.3 5.6 4.6 5.7 4.6 6.1 4.5 6.5 4.4

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 15 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

16

4. [Floor standing (Concealed type)] CAPACITY TABLES

4. [Floor standing (Concealed type)]4-1. Cooling capacity with PURY-(E)M200-250YNW-A1

4-2. Cooling capacity with PURY-(E)M300-350YNW-A1

4-3. Cooling capacity with PURY-(E)M400-500YNW-A1

PFFY-WP-VLRMM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.5 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.6 2.5 1.6

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6

40 (4.5) 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.4 4.6 3.4 4.9 3.3 5.2 3.2

50 (5.6) 5.0 3.9 5.2 4.0 5.5 4.0 5.6 4.2 5.8 4.2 6.0 4.1 6.4 4.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-WP-VLRMM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.5 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.6 2.5 1.6

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6

40 (4.5) 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.4 4.6 3.4 4.9 3.3 5.2 3.2

50 (5.6) 5.0 3.9 5.2 4.0 5.5 4.0 5.6 4.2 5.8 4.2 6.0 4.1 6.4 4.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-WP-VLRMM-E CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.5 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.6 2.4 1.6 2.5 1.6

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.7 2.7 3.9 2.7 4.2 2.6

40 (4.5) 4.0 3.1 4.1 3.2 4.3 3.2 4.5 3.4 4.6 3.3 4.9 3.3 5.2 3.3

50 (5.6) 5.0 3.9 5.1 4.0 5.4 3.9 5.6 4.2 5.7 4.2 6.1 4.1 6.5 4.1

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 16 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

17

4. [Floor standing (Concealed type)] CAPACITY TABLES

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.2 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.3 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.2

50 (5.6) 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 17 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

18

5. [All indoor units] CAPACITY TABLES

5. [All indoor units]5-1. Heating capacity with PURY-(E)M200-250YNW-A1

5-2. Heating capacity with PURY-(E)M300-350YNW-A1

5-3. Heating capacity with PURY-(E)M400-500YNW-A1

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.1 1.0

15 (1.9) 1.9 1.9 1.5 1.3

20 (2.5) 2.5 2.5 2.0 1.8

25 (3.2) 3.2 3.2 2.6 2.2

32 (4.0) 4.0 4.0 3.2 2.8

40 (5.0) 5.1 5.0 4.0 3.5

50 (6.3) 6.4 6.3 5.0 4.4

63 (8.0) 8.1 8.0 6.4 5.6

71 (9.0) 9.1 9.0 7.2 6.3

80 (10.0) 10.1 10.0 8.0 7.0

100 (12.5) 12.6 12.5 10.0 8.8

125 (16.0) 16.2 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.0 0.9

15 (1.9) 1.9 1.9 1.4 1.2

20 (2.5) 2.6 2.5 1.9 1.6

25 (3.2) 3.3 3.2 2.4 2.0

32 (4.0) 4.1 4.0 3.0 2.6

40 (5.0) 5.1 5.0 3.7 3.2

50 (6.3) 6.5 6.3 4.7 4.0

63 (8.0) 8.2 8.0 6.0 5.1

71 (9.0) 9.2 9.0 6.7 5.8

80 (10.0) 10.2 10.0 7.5 6.4

100 (12.5) 12.8 12.5 9.3 8.0

125 (16.0) 16.4 16.0 11.9 10.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.1 1.0

15 (1.9) 1.9 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.5 2.3

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.1 5.0 4.0 3.5

50 (6.3) 6.4 6.3 5.0 4.5

63 (8.0) 8.2 8.0 6.3 5.7

71 (9.0) 9.2 9.0 7.1 6.4

80 (10.0) 10.2 10.0 7.9 7.1

100 (12.5) 12.8 12.5 9.9 8.9

125 (16.0) 16.3 16.0 12.7 11.3

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 18 ページ 2019年3月1日 金曜日 午前10時41分

MEES18K106

CA

PA

CIT

Y T

AB

LE

S

19

5. [All indoor units] CAPACITY TABLES

5-4. Heating capacity with PURY-(E)M200-250YNW-A1 "COP priority mode"

5-5. Heating capacity with PURY-(E)M300-350YNW-A1 "COP priority mode"

5-6. Heating capacity with PURY-(E)M400-500YNW-A1 "COP priority mode"

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.5 1.4 1.1 1.0

15 (1.9) 2.0 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.6 2.2

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.2 5.0 4.0 3.5

50 (6.3) 6.5 6.3 5.0 4.4

63 (8.0) 8.3 8.0 6.4 5.6

71 (9.0) 9.3 9.0 7.2 6.3

80 (10.0) 10.4 10.0 8.0 7.0

100 (12.5) 12.9 12.5 10.0 8.8

125 (16.0) 16.6 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.5 1.4 1.1 1.0

15 (1.9) 2.0 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.6 2.2

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.2 5.0 4.0 3.5

50 (6.3) 6.5 6.3 5.0 4.4

63 (8.0) 8.3 8.0 6.4 5.6

71 (9.0) 9.3 9.0 7.2 6.3

80 (10.0) 10.4 10.0 8.0 7.0

100 (12.5) 12.9 12.5 10.0 8.8

125 (16.0) 16.6 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.0 0.9

15 (1.9) 1.9 1.9 1.4 1.2

20 (2.5) 2.6 2.5 1.9 1.6

25 (3.2) 3.3 3.2 2.4 2.0

32 (4.0) 4.1 4.0 3.0 2.6

40 (5.0) 5.1 5.0 3.7 3.2

50 (6.3) 6.5 6.3 4.7 4.0

63 (8.0) 8.2 8.0 6.0 5.1

71 (9.0) 9.2 9.0 6.7 5.8

80 (10.0) 10.2 10.0 7.5 6.4

100 (12.5) 12.8 12.5 9.3 8.0

125 (16.0) 16.4 16.0 11.9 10.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005141.BOOK 19 ページ 2019年3月1日 金曜日 午前10時41分

20MEES18K106

CAPACITY TABLES

0000005141.BOOK 20 ページ 2019年3月1日 金曜日 午前10時41分

Capacity Tables

MEES18K111 1

CONTENTS CAPACITY TABLES

I.CAPACITY TABLES

1. [Ceiling concealed (Low static pressure type)] ......................................................................................... 2

1-1. Cooling capacity with PUHY-(E)M200-250YNW-A1........................................................................ 21-2. Cooling capacity with PUHY-(E)M300-350YNW-A1........................................................................ 21-3. Cooling capacity with PUHY-(E)M400-500YNW-A1........................................................................ 2

2. [Ceiling concealed (Medium static pressure type)] ................................................................................... 3

2-1. Cooling capacity with PUHY-(E)M200-250YNW-A1........................................................................ 32-2. Cooling capacity with PUHY-(E)M300-350YNW-A1........................................................................ 32-3. Cooling capacity with PUHY-(E)M400-500YNW-A1........................................................................ 4

3. [Floor standing (Concealed type)]............................................................................................................. 5

3-1. Cooling capacity with PUHY-(E)M200-250YNW-A1........................................................................ 53-2. Cooling capacity with PUHY-(E)M300-350YNW-A1........................................................................ 53-3. Cooling capacity with PUHY-(E)M400-500YNW-A1........................................................................ 5

4. [All indoor units] ........................................................................................................................................ 6

4-1. Heating capacity with PUHY-(E)M200-250YNW-A1........................................................................ 64-2. Heating capacity with PUHY-(E)M300-350YNW-A1........................................................................ 64-3. Heating capacity with PUHY-(E)M400-500YNW-A1........................................................................ 64-4. Heating capacity with PUHY-(E)M200-250YNW-A1 “Capacity priority mode”................................. 74-5. Heating capacity with PUHY-(E)M300-350YNW-A1 “Capacity priority mode”................................. 74-6. Heating capacity with PUHY-(E)M400-500YNW-A1 “Capacity priority mode”................................. 7

0000005140.BOOK 1 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

2

1. [Ceiling concealed (Low static pressure type)] CAPACITY TABLES

I.CAPACITY TABLES1. [Ceiling concealed (Low static pressure type)]1-1. Cooling capacity with PUHY-(E)M200-250YNW-A1

1-2. Cooling capacity with PUHY-(E)M300-350YNW-A1

1-3. Cooling capacity with PUHY-(E)M400-500YNW-A1

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.5 4.1 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.9 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.5 4.1 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.9 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMS-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

10 (1.2) 1.1 0.9 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.4 1.0

15 (1.7) 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.5

20 (2.2) 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5

40 (4.5) 4.0 3.0 4.1 3.1 4.3 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.1 3.9 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 2 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

3

2. [Ceiling concealed (Medium static pressure type)] CAPACITY TABLES

2. [Ceiling concealed (Medium static pressure type)]2-1. Cooling capacity with PUHY-(E)M200-250YNW-A1

2-2. Cooling capacity with PUHY-(E)M300-350YNW-A1

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.2 4.6 5.5 4.5 5.6 4.9 5.8 4.8 6.0 4.8 6.4 4.7

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.4 7.7 5.3 8.1 5.3

71 (8.0) 7.2 5.4 7.4 5.6 7.8 5.5 8.0 5.9 8.2 5.8 8.6 5.7 9.2 5.6

80 (9.0) 8.1 5.9 8.3 6.0 8.8 6.0 9.0 6.3 9.3 6.2 9.7 6.1 10.3 6.0

100 (11.2) 10.0 8.0 10.3 8.3 10.9 8.2 11.2 8.7 11.5 8.6 12.1 8.5 12.8 8.4

125 (14.0) 12.5 9.7 12.9 10.0 13.7 9.8 14.0 10.4 14.4 10.4 15.1 10.2 16.0 10.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.1 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.4 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.2 5.2 5.5 5.5 5.6 5.6 5.8 5.8 6.0 6.0 6.4 6.4

63 (7.1) 6.4 6.4 6.5 6.5 6.9 6.9 7.1 7.1 7.3 7.3 7.7 7.7 8.1 8.1

71 (8.0) 7.2 7.2 7.4 7.4 7.8 7.8 8.0 8.0 8.2 8.2 8.6 8.6 9.2 8.5

80 (9.0) 8.1 8.1 8.3 8.3 8.8 8.5 9.0 9.0 9.3 9.1 9.7 9.0 10.3 8.9

100 (11.2) 10.0 9.1 10.3 9.4 10.9 9.3 11.2 10.0 11.5 9.9 12.1 9.8 12.8 9.6

125 (14.0) 12.5 10.2 12.9 10.6 13.7 10.4 14.0 11.1 14.4 11.0 15.1 10.8 16.0 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9

25 (2.8) 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1

32 (3.6) 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.2 4.6 5.5 4.5 5.6 4.9 5.8 4.8 6.0 4.8 6.4 4.7

63 (7.1) 6.4 5.1 6.5 5.2 6.9 5.2 7.1 5.5 7.3 5.4 7.7 5.3 8.1 5.3

71 (8.0) 7.2 5.4 7.4 5.6 7.8 5.5 8.0 5.9 8.2 5.8 8.6 5.7 9.2 5.6

80 (9.0) 8.1 5.9 8.3 6.0 8.8 6.0 9.0 6.3 9.3 6.2 9.7 6.1 10.3 6.0

100 (11.2) 10.0 8.0 10.3 8.3 10.9 8.2 11.2 8.7 11.5 8.6 12.1 8.5 12.8 8.4

125 (14.0) 12.5 9.7 12.9 10.0 13.7 9.8 14.0 10.4 14.4 10.4 15.1 10.2 16.0 10.0

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.1 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.4 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.2 5.2 5.5 5.5 5.6 5.6 5.8 5.8 6.0 6.0 6.4 6.4

63 (7.1) 6.4 6.4 6.5 6.5 6.9 6.9 7.1 7.1 7.3 7.3 7.7 7.7 8.1 8.1

71 (8.0) 7.2 7.2 7.4 7.4 7.8 7.8 8.0 8.0 8.2 8.2 8.6 8.6 9.2 8.5

80 (9.0) 8.1 8.1 8.3 8.3 8.8 8.5 9.0 9.0 9.3 9.1 9.7 9.0 10.3 8.9

100 (11.2) 10.0 9.1 10.3 9.4 10.9 9.3 11.2 10.0 11.5 9.9 12.1 9.8 12.8 9.6

125 (14.0) 12.5 10.2 12.9 10.6 13.7 10.4 14.0 11.1 14.4 11.0 15.1 10.8 16.0 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 3 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

4

2. [Ceiling concealed (Medium static pressure type)] CAPACITY TABLES

2-3. Cooling capacity with PUHY-(E)M400-500YNW-A1

PEFY-W-VMA(L)-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.5 1.9

25 (2.8) 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1

32 (3.6) 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5

40 (4.5) 4.0 3.3 4.1 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5

50 (5.6) 5.0 4.4 5.1 4.6 5.4 4.5 5.6 4.9 5.7 4.8 6.1 4.8 6.5 4.7

63 (7.1) 6.3 5.0 6.4 5.2 6.8 5.1 7.1 5.5 7.3 5.4 7.7 5.4 8.2 5.3

71 (8.0) 7.1 5.4 7.2 5.5 7.7 5.5 8.0 5.9 8.2 5.8 8.7 5.7 9.2 5.6

80 (9.0) 8.0 5.9 8.1 6.0 8.7 5.9 9.0 6.3 9.2 6.2 9.8 6.2 10.4 6.1

100 (11.2) 10.0 8.0 10.1 8.2 10.8 8.1 11.2 8.7 11.5 8.6 12.2 8.5 12.9 8.4

125 (14.0) 12.5 9.6 12.7 9.9 13.5 9.8 14.0 10.4 14.4 10.4 15.2 10.2 16.1 10.1

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PEFY-W-VMA2-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 2.0 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5

25 (2.8) 2.5 2.5 2.5 2.5 2.7 2.7 2.8 2.8 2.9 2.9 3.0 3.0 3.2 3.2

32 (3.6) 3.2 3.2 3.3 3.3 3.5 3.5 3.6 3.6 3.7 3.7 3.9 3.9 4.2 4.0

40 (4.5) 4.0 4.0 4.1 4.1 4.3 4.1 4.5 4.5 4.6 4.4 4.9 4.4 5.2 4.3

50 (5.6) 5.0 5.0 5.1 5.1 5.4 5.4 5.6 5.6 5.7 5.7 6.1 6.1 6.5 6.5

63 (7.1) 6.3 6.3 6.4 6.4 6.8 6.8 7.1 7.1 7.3 7.3 7.7 7.7 8.2 8.2

71 (8.0) 7.1 7.1 7.2 7.2 7.7 7.7 8.0 8.0 8.2 8.2 8.7 8.6 9.2 8.5

80 (9.0) 8.0 8.0 8.1 8.1 8.7 8.4 9.0 9.0 9.2 9.1 9.8 9.0 10.4 8.9

100 (11.2) 10.0 9.0 10.1 9.3 10.8 9.3 11.2 10.0 11.5 9.9 12.2 9.8 12.9 9.7

125 (14.0) 12.5 10.2 12.7 10.4 13.5 10.4 14.0 11.1 14.4 11.0 15.2 10.9 16.1 10.7

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 4 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

5

3. [Floor standing (Concealed type)] CAPACITY TABLES

3. [Floor standing (Concealed type)]3-1. Cooling capacity with PUHY-(E)M200-250YNW-A1

3-2. Cooling capacity with PUHY-(E)M300-350YNW-A1

3-3. Cooling capacity with PUHY-(E)M400-500YNW-A1

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.1

50 (5.6) 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.0 4.0 6.4 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

PFFY-W-VCM-A CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 21.5°C D.B. 23°C D.B. 25°C D.B. 27°C D.B. 28°C D.B. 30°C D.B. 32°C D.B.

(Rated kW) 15°C W.B. 16°C W.B. 18°C W.B. 19°C W.B. 20°C W.B. 22°C W.B. 24°C W.B.

CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

20 (2.2) 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7

25 (2.8) 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0

32 (3.6) 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.2 2.4

40 (4.5) 4.0 3.0 4.1 3.1 4.3 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.2

50 (5.6) 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 5 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

6

4. [All indoor units] CAPACITY TABLES

4. [All indoor units]4-1. Heating capacity with PUHY-(E)M200-250YNW-A1

4-2. Heating capacity with PUHY-(E)M300-350YNW-A1

4-3. Heating capacity with PUHY-(E)M400-500YNW-A1

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.5 1.4 1.1 1.0

15 (1.9) 2.0 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.6 2.2

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.2 5.0 4.0 3.5

50 (6.3) 6.5 6.3 5.0 4.4

63 (8.0) 8.3 8.0 6.4 5.6

71 (9.0) 9.3 9.0 7.2 6.3

80 (10.0) 10.4 10.0 8.0 7.0

100 (12.5) 12.9 12.5 10.0 8.8

125 (16.0) 16.6 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.5 1.4 1.1 1.0

15 (1.9) 2.0 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.6 2.2

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.2 5.0 4.0 3.5

50 (6.3) 6.5 6.3 5.0 4.4

63 (8.0) 8.3 8.0 6.4 5.6

71 (9.0) 9.3 9.0 7.2 6.3

80 (10.0) 10.4 10.0 8.0 7.0

100 (12.5) 12.9 12.5 10.0 8.8

125 (16.0) 16.6 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.0 0.9

15 (1.9) 1.9 1.9 1.4 1.2

20 (2.5) 2.6 2.5 1.9 1.6

25 (3.2) 3.3 3.2 2.4 2.0

32 (4.0) 4.1 4.0 3.0 2.6

40 (5.0) 5.1 5.0 3.7 3.2

50 (6.3) 6.5 6.3 4.7 4.0

63 (8.0) 8.2 8.0 6.0 5.1

71 (9.0) 9.2 9.0 6.7 5.8

80 (10.0) 10.2 10.0 7.5 6.4

100 (12.5) 12.8 12.5 9.3 8.0

125 (16.0) 16.4 16.0 11.9 10.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 6 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K111

CA

PA

CIT

Y T

AB

LE

S

7

4. [All indoor units] CAPACITY TABLES

4-4. Heating capacity with PUHY-(E)M200-250YNW-A1 “Capacity priority mode”

4-5. Heating capacity with PUHY-(E)M300-350YNW-A1 “Capacity priority mode”

4-6. Heating capacity with PUHY-(E)M400-500YNW-A1 “Capacity priority mode”

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.1 1.0

15 (1.9) 1.9 1.9 1.5 1.3

20 (2.5) 2.5 2.5 2.0 1.8

25 (3.2) 3.2 3.2 2.6 2.2

32 (4.0) 4.0 4.0 3.2 2.8

40 (5.0) 5.1 5.0 4.0 3.5

50 (6.3) 6.4 6.3 5.0 4.4

63 (8.0) 8.1 8.0 6.4 5.6

71 (9.0) 9.1 9.0 7.2 6.3

80 (10.0) 10.1 10.0 8.0 7.0

100 (12.5) 12.6 12.5 10.0 8.8

125 (16.0) 16.2 16.0 12.8 11.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.0 0.9

15 (1.9) 1.9 1.9 1.4 1.2

20 (2.5) 2.6 2.5 1.9 1.6

25 (3.2) 3.3 3.2 2.4 2.0

32 (4.0) 4.1 4.0 3.0 2.6

40 (5.0) 5.1 5.0 3.7 3.2

50 (6.3) 6.5 6.3 4.7 4.0

63 (8.0) 8.2 8.0 6.0 5.1

71 (9.0) 9.2 9.0 6.7 5.8

80 (10.0) 10.2 10.0 7.5 6.4

100 (12.5) 12.8 12.5 9.3 8.0

125 (16.0) 16.4 16.0 11.9 10.2

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

All Indoor units SHC: Sensible Heat Capacity (kW)

Model Indoor air temp.

size 15°C D.B. 20°C D.B. 25°C D.B. 27°C D.B.

(Rated kW) SHC SHC SHC SHC

10 (1.4) 1.4 1.4 1.1 1.0

15 (1.9) 1.9 1.9 1.5 1.3

20 (2.5) 2.6 2.5 2.0 1.8

25 (3.2) 3.3 3.2 2.5 2.3

32 (4.0) 4.1 4.0 3.2 2.8

40 (5.0) 5.1 5.0 4.0 3.5

50 (6.3) 6.4 6.3 5.0 4.5

63 (8.0) 8.2 8.0 6.3 5.7

71 (9.0) 9.2 9.0 7.1 6.4

80 (10.0) 10.2 10.0 7.9 7.1

100 (12.5) 12.8 12.5 9.9 8.9

125 (16.0) 16.3 16.0 12.7 11.3

* The capacity does not depend on the outdoor temperature. kcal/h = kW x 860, BTU/h = kW x 3,412

0000005140.BOOK 7 ページ 2019年2月28日 木曜日 午後4時57分

8MEES18K111

CAPACITY TABLES

0000005140.BOOK 8 ページ 2019年2月28日 木曜日 午後4時57分

MEES18K071New publication effective Mar. 2019

Specifications subject to change without notice

WarningDo not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.- It may also be in violation of applicable laws.- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong

type of refrigerant.Our air conditioning equipment and heat pumps contain a fluorinated greenhouse gas, R32.