A New Generation of Aerosol Fire
Suppression System
Manufactured and Designed byManufactured and Designed byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Manual Operation, Installation and Commissioning
Distributor and Installer
TECHNICQAL SDN. BHD.
MANUAL OPERATION – Control Panel
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AEROHUB ® CONVENTIONAL CONTROL PANEL
In Normal Condition:- “AC ON”, “DC ON” and “CHARGER ON”
This Aerohub® Control Panel got 2 power source:-a) Supply from TNB -- 240VACb) Battery 24VDC ___AH – up to 3 days of standby if the AC supply fails.
MANUAL OPERATION – Control Panel
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
If the AC Fails the buzzer will sound and indicator “CHARGER FAIL” & “MAINS FAIL” will light ON.
If the Battery is Faulty or connection is loose the buzzer also will sound and indicator “BATTERY FAIL” will light ON.
Open the Aerohub® Control Panel, Switch for the buzzer is located behind the Main Board and have 2 Toggle switch :- 1) BELL OFF
2) BUZZER OFF
MANUAL OPERATION – Smoke Detector
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Smoke Detector S65 (Apollo)
4 meter
Height : 4 meter
4 meter
4 meter4 meter
Coverage for Smoke Detector
MANUAL OPERATION – Smoke Detector
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
SMOKE DETECTOR
Zone 1 = Smoke Detector activate / trigger :- Sense Smoke Fine dust Cable short circuit
In this situation the indicator L.E.D at zone 1 will light ON.
When Smoke Detector is Trigger:-
1) The Bell will be intermittent ringing,2) RED Bulb at Twins Flashing Light will be blinking.
MANUAL OPERATION – Heat Detector
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Heat Detector S60 (Apollo)
3.5 meter
Height : 4 meter
3.5 meter
3.5 meter3.5 meter
Coverage for Heat Detector
MANUAL OPERATION – Heat Detector
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
HEAT DETECTOR
Zone 2 = Smoke Detector activate / trigger- Sense Heat (Temperature 58oC) Cable shorted
In this situation the indicator L.E.D at zone 2 will light ON.
When Smoke Detector is Trigger:-
1) The Bell intermittent ringing ,2) RED Bulb at Twins Flashing Light will blinking.
MANUAL OPERATION – Control Panel
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AIR-COND TRIP.
AIR-COND TRIP WHEN:-
1) When zone 1 & 2 are triggered, Aerohub® Control Panel will send voltage 24VDC to the DB Air-Cond,
2) If only 1 zone is triggered i.e., zone 1 or zone 2 Aerohub® Control Panel will not send Voltage 24VDC to DB Air-Cond.
MANUAL OPERATION – Alarm Bell
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
ALARM BELL
In Normal condition the Alarm Bell not ringing,
Alarm Bell ringing if:- Zone 1 Smoke Detector -- trigger /, Zone 2 Heat Detector -- trigger
Stop the Alarm Bell from Ringing :-
1) Open the Aerohub® Main Board Control Panel:- 1) BELL OFF
2) BUZZER OFF
2) Switch the BELL OFF and the bell stop ringingSwitch the BUZZER OFF and the sound will stop.
MANUAL OPERATION – Twins Flashing Light
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
TWINS FLASHING LIGHT
In Normal condition only GREEN Bulb will be light ON,
Twins Flashing Light RED Bulb will blinking / function if:- Zone 1 Smoke Detector -- trigger
/ Zone 2 Heat Detector -- trigger.
MANUAL OPERATION – KeySwitch
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
KEYSWICTH / MANUAL DISCHARGE:-
1) Keyswitch / Manual Discharged* To manually discharged the Aerohub® Fire Suppression,
-- Not waiting time delay of 25-30 second after of zone 1 & 2 is trigger.
MANUAL OPERATION – Auto/Manual Switch
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AUTO / MANUAL :-
1) AUTO * In Normal condition the position of the key must be in AUTO.
2) MANUAL* If maintenance is being done inside the room, please turn to MANUAL, this is to prevent from accidentally discharged, but the system is in normal operation.
MANUAL OPERATION – Aerohub® Generator
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
SS/MS 50
SS/MS 30
SS/MS 20
SS/MS 10
SS/MS 5
SS/MS 2.5
50m3 30m3 20m3 10m3 5m3 2.5m3
GENERATOR SPECIFICATIONS :
• Generator housing and all internal components are made of Stainless Steel or Mild Steel to suit the environment.
• Temperature : Operates with +50 to -50 °C
• Humidity : Operates up to 96% RH
• Warranty : 2 years for manufacturer’s defect.
• Voltage : 24V dc 1.5A
Colour of Wiring Cable
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Colour of Cable
Wiring Accerssories
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Termination of Accerssories Detector
Drawing of Installation
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Drawing
Conduit G.I (Installation)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AERO-HUB®
KeySwitch Auto/Manual Switch
Alarm Bell
Twins Flashing Light
Heat DetectorSmoke Detector
AEROHUB® control Panel
Sample Layout Installation of GI. Conduit
Wiring Cable
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
1.5mm single cable
1.5mm single cable
Layout Wiring Colour
Testing, Commissioning & Handover
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Testing, Commissioning & HandOver Form
T, C & H – (Step -1)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
Note:-1) Please disconnect all Cable from Aerohub Canister.
This is to prevent from accidentally discharge Aerohub® Fire Suppression System.
1) MAINS ON/OFF2) CHARGER ON
i) Check AC Supply with Test-pen or Analog Meter (240V AC)
ii) Switch ON and OFF to check the switch is in good condition
T, C & H – (Step -2)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
3) BATTERY FAIL
i) Open the fuse (Battery Fuse), When you do this the buzzer will be sound and LED “Battery Fail” will light ON,
ii) Use Analog meter to check the Battery is in good Condition per cell voltage Battery is 12V DC above,
iii) After finish check Battery voltage, Close back (Battery Fuse). The sound and L.E.D indicator “Battery Fail” will be in OFF within 10 – 15 second.
T, C & H – (Step -3)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
4) TEST L.E.D
i) ON L.E.D toggle switch and all LED light “ON”,
ii) Check all toggle switch at main frame weather it is in condition,
iii) If you press alarm button the RED LED will light, Alarm Bell rigging and Twins Flashing Light Bulb change from GREEN to RED, to make it NORMAL condition back “ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -4)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
5) SMOKE DETECTOR
i) Test Smoke Detector is in condition or not, use Smoke Tester,
ii) Spray Smoke Tester, when u do this the L.E.D at Zone 1 light “ON”, Alarm Bell will rigging intermittent, Twins Flashing Light Bulb change from GREEN to RED,
iii) To make it in NORMAL back “ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -5)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
6) HEAT DETECTOR
i) Test Heat Detector in condition or not use Hair Dryer,
ii) Heat-up -- when u do this the L.E.D at Zone 2 light “ON”, the Alarm Bell rigging intermittent and Twins Flashing Light Bulb change from GREEN to RED,
iii) To make it in NORMAL condition back “ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -6)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
7) ALARM BELL
i) Test Alarm Bell is in good condition is press alarm button at zone 1 / zone 2,
ii) To make it in NORMAL condition back “ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -7)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
8) TWINS FLASHING LIGHT
i) In NORMAL green Bulb light ON.
ii) Test Twins Flashing Light is in good condition is press alarm button at zone 1 / zone 2, -- RED Bulb light “ON” and GREEN Bulb will OFF,
i) To make it in NORMAL condition back ‘ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -8)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
9) KEYSWITCH / MANUAL RELEASE
i) Test keyswitch is in good condition is to turn ON and L.E.D Aero Discharged will light “ON”,
ii) To make it in NORMAL condition back is turn OFF back KeySwitch.
T, C & H – (Step -9)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AUTO / MANUAL :-
1) AUTO * In Normal condition the position of the key must be in AUTO.
2) MANUAL* Under maintenance turn to MANUAL,
this is to prevent from accidentally discharged, but the system is in NORMAL
mood operation system.
T, C & H – (Step -11)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AIR-COND TRIP.
AIR-COND TRIP WHEN:-
1) Press alarm button zone 1 and zone 2, Aerohub® Control Panel will send voltage 24VDC to the DB Air-Cond ,
2) If only 1 zone is triggered i.e., zone 1 or zone 2 Aerohub® Control Panel will not send voltage 24VDC to DB Air-Cond,
3) To make it in NORMAL, “ISO” isolate the alarm and press ALARM RESET.
T, C & H – (Step -12)
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD
AEROHUB ® DISCHARGED 25 -30 SECOND
1) Press alarm button zone 1 and zone 2, after 25 – 30 second Aerohub ® Discharged LED will light ON,
2) After Aerohub® Discharged LED light ON, take Analog / Digital meter and check all terminal of Aerohub® have voltage 24VDC,
Designed byDesigned byHUB TECHNOLOGIES (M) SDN BHDHUB TECHNOLOGIES (M) SDN BHD