EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of acces-sories for underground cables: pre-moulded EPDM or silicone rubber connectors, terminationsand joints for cables and epoxy bushings for transformers and switch gear, as well as a large range of cold-shrinkable terminations and joints from �2 to 42 kV.Euromold is also the manufac-turer of electrical components for the high voltage accessories of the Nexans group.
ISO 9001 CertificateSince �992, Euromold’s commitment to quality is demonstrated by its ISO 900� certification.
Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELTEST accredi-tation no.�92-T-ISO �7025 conform with the European standards for laboratories ISO �7025 for electrical testing of medium voltage cable acces-sories according to the Inter-national standards IEC 6�442 and HD 629.
International standardsAll our products meet the International standards like CENELEC HD 629.�, CENELEC EN 50�80, IEC 60�37, IEEE 386 & 404… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.
2
TERMINATIONS
Table of contentsITK - indoor terminationOTK - outdoor terminationAIN - indoor terminationAFN - outdoor terminationT-ITK - 3-core indoor terminationT-OTK - 3-core outdoor termination�5TS-NSS - universal bushing boot
3
ITKINDOOR TERMINATIONS
ApplicationA kit of 3 terminations for use indoors in controlled environmental conditions and subject to light condensation.To connect polymeric insulated cable to equipment.
DesignIndoor termination comprising:�. Cable lug (not included in
the standard kit).2. Water sealing mastic.3. Silicone tube.4. Stress control mastic.5. Conductive EPDM ring.
Specifications and standardsMeets the requirements of CENELEC HD 629.�.
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV
Terminationtype
VoltageUm(kV)
Strikedistance L
(mm)
Diameter overcore insulation
(mm)
Conductorsizes
(mm2)
min. max. min. max.ITK 2�2
ITK 3�2
ITK 224
ITK 324
�2
�2
24
24
260
300
260
300
�4
30
�4
30
33
50
33
50
50
400
25
300
400
�000
240
800
Up to 24 kV
L
3
1
2
4
5
2
4
Kit contentsThe complete ITK termination kit comprises the following components:
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable insulation diameter in mm.
Example:The copper wire screened cable is �2 kV, �50 mm2 stranded aluminium.The diameter over core insulation is 26.2 mm.Order a 3 x ITK 2�2 termination kit.
For use with copper wire screened cables.
No earthing device is
necessary.
For use withcopper tape
screened cables. Also order a Kit MT.
3 x Factory pre-assembled silicone tubes
comprising stress relief and sealing mastic.
3 x ITK 2�2 or ITK 224 termination kit
All commercialised European standard
cable lugs can be used.
Cable lugs should be within the dimensions
specified (not applicable for ITK 3�2 and
ITK 324).
Orderingpart
number
VoltageUm(kV)
Diameter overcore insulation
(mm)
Conductorsizes
(mm2)
min. max. min. max.3 x ITK 2�2
3 x ITK 3�2
3 x ITK 224
3 x ITK 324
�2
�2
24
24
�4
30
�4
30
33
50
33
50
50
400
25
300
400
�000
240
800
=
The kit also comprises water sealing mastic
and installation instructions.
3 x Factory pre-assembled silicone tubes
comprising stress relief and sealing mastic.
3 x ITK 3�2 or ITK 324 termination kit
=
Can be supplied with all common types of
cable lugs.
For use with Alupe or C 33-226 cables.
Please contact our representative.
For use with three-core cables:
see T-ITK.
If the cable lug barrel diameter (A) is less
than 20 mm:order a rubber
adapting sleeve.
40 mm min.
110 mm max.
46 mmmax.
A
5
OTKOUTDOOR TERMINATIONS
ApplicationA kit of 3 terminations for use outdoors and exposed to prolonged sunshine and other weather conditions. To connect polymeric insulated cable to equipment and for the outdoor terminating on to overhead lines or bus bars.
DesignOutdoor terminationcomprising:�. Cable lug (not included in
the standard kit). 2. Water sealing mastic. 3. Sheds which can be installed
upwards or down. 4. Silicone tube with sheds. 5. Silicone tube. 6. Stress control mastic. 7. Conductive EPDM ring.
Specifications and standardsMeets the requirements of CENELEC HD 629.�.
Up to 24 kV
Terminationtype
VoltageUm(kV)
Creepage distance A-B
(mm)
Strikedistance “L”
(mm)
Diameter overcore insulation
(mm)Numberof sheds
Conductorsizes
(mm2)Fig.no.
min. max. min. max.OTK 2�2
OTK 3�2
OTK 224
OTK 324
�2
�2
24
24
420
890
600
890
300
650
400
650
�4
30
�9
30
33
50
33
50
3
6
5
6
50
500
50
300
400
�000
240
630
�
3
2
3
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV
4
1
7
3
A
B
2
6
2
L
A1
4
3
5
2
6
2
7B
L
A1
4
3
5
2
6
2
7B
L
Fig. � Fig. 2 Fig. 3
6
3 x Factory pre-assembled silicone tubes comprising stress relief and sealing mastic.
3 x Silicone tube with 5 sheds
3 x Silicone tube with 6 sheds
3 x Factory pre-assembled silicone tubes comprising stress relief and sealing mastic.
3 x Factory pre-assembled silicone tubes comprising stress relief and sealing mastic.
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable insulation diameter in mm.
Example:The copper wire screened cable is 24 kV, �50 mm2 stranded aluminium.The diameter over core insulation is 26.2 mm.Order a 3 x OTK 224 termination kit.
All commercialised European standard
cable lugs can be used.
Cable lugs should be within the dimensions
specified (not applicable for OTK 3�2 and
OTK 324).
Orderingpart
number
VoltageUm(kV)
Diameter overcore insulation
(mm)
Conductorsizes
(mm2)
min. max. min. max.3 x OTK 2�2
3 x OTK 3�2
3 x OTK 224
3 x OTK 324
�2
�2
24
24
�4
30
�9
30
33
50
33
50
50
500
50
300
400
�000
240
800
Kit contentsThe complete OTK termination kit comprises the following components:
The kit also comprises water sealing mastic
and installation instructions.
3 x OTK 224
termination kit=+
+
For use with copper wire screened cables.
No earthing device is
necessary.
For use withcopper tape
screened cables. Also order a Kit MT.
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
For use with Alupe or C 33-226 cables.
Please contact our representative.
For use with three-core cables:
see T-OTK.
Can be supplied with all common types of
cable lugs.
3 x OTK 3�2
or
3 x OTK 324
termination kit
=
3 x OTK 2�2
termination kit=
40 mm min.
110 mm max.
46 mmmax.
7
AININDOOR TERMINATIONS
ApplicationA kit of 3 terminations for use indoors in controlled environmental conditions and subject to light condensation. Provides a simple and quick method of stress relieving on screened polymeric cables.
DesignIndoor termination comprising:�. Cable lug (not included in
the standard kit). 2. High flexibility silicone
rubber housing, allowing larger tolerances on cable insulation diameters, with integrated conductive rubber insert, providing stress relief.
3. Earthing lug (not included in the standard kit).
Specifications and standardsMeets the requirements of CENELEC HD 629.� and IEC 60502-4.
Up to 42 kV
Terminationtype
VoltageUm(kV)
Conductor sizes(mm2)
min. max.
AIN �0
AIN 20
AIN 30
AIN 36
�2
24
36
42
25
35
50
�50
�000
�000
800
800
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV
20.8/36 (41.5) kV
1
2
3
8
Example:A set of 3 indoor terminations for a 24 kV - 240 mm2 stranded aluminium cable with copper wire screen without cable lugs. The diameter over core insulation is 30.4 mm.Order a 3 x AIN 20-2-H termination kit.
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable dimensions in mm.
Kit contentsA kit always comprises 3 termination housings, installation instructions, special lubricant, wiper, adhesive tape, field control mastic, ...Cable lugs and earthing lugs are not included in the standard kit, but can be ordered separately.
Voltage
Um
(kV)
Conductor
sizes
(mm2)
Diameter over
core insulation
(mm)
Number
of sheds
L
(mm)
Dia. D
(mm)
Ordering
part number
min. max. min. max.
�2
25
�20
300
800
95
240
500
�000
�3.5
�9.4
27.4
40.0
20.8
28.4
36.6
55.0
2
2
2
7
�50
�50
�50
330
37
43
60
�27
3 x AIN �0-�-H
3 x AIN �0-2-H
3 x AIN �0-3-H
3 x AIN �0-4-H
24
35
95
300
500
70
240
630
�000
�8.3
23.0
3�.6
40.0
23.4
32.6
43.5
55.0
3
3
3
7
225
225
225
330
47
56
62
�27
3 x AIN 20-�-H
3 x AIN 20-2-H
3 x AIN 20-3-H
3 x AIN 20-4-H
36
50
95
240
400
70
240
400
800
24.2
27.3
3�.5
40.0
28.4
37.6
42.8
55.0
6
6
6
7
300
300
300
330
74
74
8�
�27
3 x AIN 30-�-H
3 x AIN 30-2-H
3 x AIN 30-3-H
3 x AIN 30-4-H
42�50
400
300
800
3�.5
40.0
42.8
55.0
7
7
330
330
�27
�27
3 x AIN 36-3-H
3 x AIN 36-4-H
For use with copper wire screened cables.
No earthing device is
necessary.
For use withcopper tape
screened cables. Order: -/MT.
For use with three-core cables.
Please contact our representative.
For use with other cable types.
Please contact our representative.
Can be supplied with all common types of
cable lugs.
No heating or flame is required.
L
dia. D
9
AFNOUTDOOR TERMINATIONS
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV
20.8/36 (41.5) kV
Up to 42 kVApplicationA kit of 3 terminations for use outdoors and exposed to prolonged sunshine and other weather conditions. To connect polymeric insulated cable to equipment and for the outdoor terminating on to overhead lines or bus bars.
DesignOutdoor terminationcomprising:�. Cable lug (not included in
the standard kit). 2. Water sealing silicone sleeve.3. Silicone housing with sheds
and integrated conductive silicone rubber insert providing stress relief for the cable.
4. Water sealing mastic.5. Earthing clamp. 6. Earthing lug (not included in
the standard kit).
Specifications and standardsMeets the requirements of CENELEC HD 629.� and IEC 60502-4.
Terminationtype
VoltageUm(kV)
Conductor sizes(mm2)
min. max.
AFN �0
AFN 20
AFN 30
AFN 36
�2
24
36
42
25
35
50
�50
�000
�000
800
800
5
1
2
3
4
6
�0
Example:A set of 3 outdoor terminations for a 24 kV - 240 mm2 stranded aluminium cable with copper wire screen without cable lugs. The diameter over core insulation is 30.4 mm.Order a 3 x AFN 20-2-H termination kit.
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable dimensions in mm.
Kit contentsA kit always comprises 3 termination housings, water sealing sleeve, the installation instructions, special lubricant, wiper, earthing clamp, water sealing mastic, adhesive tape, field control mastic, ...Cable lugs and earthing lugs are not included in the standard kit, but can be ordered separately.
Voltage
Um
(kV)
Conductor
sizes
(mm2)
Diameter over
core insulation
(mm)
Number
of sheds
L
(mm)
Dia. D
(mm)
Creepage
distance
(mm)
Ordering
part number
min. max. min. max.
�2
25
�20
300
800
95
240
500
�000
�3.5
�9.4
27.4
40.0
20.8
28.4
36.6
55.5
3
3
3
7
�50
�50
�50
330
90
96
�05
�27
369
365
360
749
3 x AFN �0-�-H
3 x AFN �0-2-H
3 x AFN �0-3-H
3 x AFN �0-4-H
24
35
95
300
500
70
240
630
�000
�8.3
23.0
3�.6
40.0
23.4
32.6
43.5
55.5
4
4
4
7
225
225
225
330
�00
��2
��8
�27
480
499
462
749
3 x AFN 20-�-H
3 x AFN 20-2-H
3 x AFN 20-3-H
3 x AFN 20-4-H
36
50
95
240
400
70
240
400
800
24.2
27.3
3�.5
40.0
28.4
37.6
42.8
55.0
6
6
6
7
300
300
300
330
��5
��5
�27
�27
695
694
7�8
749
3 x AFN 30-�-H
3 x AFN 30-2-H
3 x AFN 30-3-H
3 x AFN 30-4-H
42�50
400
300
800
3�.5
40.0
42.8
55.0
7
7
330
330
�27
�27
749
749
3 x AFN 36-3-H
3 x AFN 36-4-H
dia. D
L
For use with copper wire screened cables.
No earthing device is
necessary.
For use withcopper tape
screened cables. Order: -/MT.
For use with three-core cables.
Please contact our representative.
For use with other cable types.
Please contact our representative.
Can be supplied with all common types of
cable lugs.
No heating or flame is required.
��
T-ITKTHREE CORE
INDOOR TERMINATIONS
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV
ApplicationThe T-ITK is a cold-shrinkable indoor termination suited for polymeric insulated three-core cables. It will provide a necessary seal against moisture penetration and a perfect electrical field control.
DesignCold-shrinkable termination comprising:�. Cable lugs (not included in
the standard kit). 2. Water sealing mastic.3. Silicone rubber tubes.4. Stress control mastic.5. Conductive EPDM ring.6. Silicone rubber protection
tubes.7. Break-out.8. Flexible tinned copper braid
(for use with individual metal tape screened cables).
Specifications and standardsThe cold-shrinkable T-ITK termination meets the requirements of CENELEC HD 629.�.
Terminationtype
VoltageUm(kV)
Diameter overcore insulation
Dia. d (mm)
Diameter overouter sheath Dia. D (mm)
Conductor sizes(for information only)
(mm2)
min. max. min. max. min. max.T-ITK �2-�
T-ITK �2-2
T-ITK 24-�
T-ITK 24-2
�2
�2
24
24
�6
26
�6
26
30
42
30
42
48
58
48
58
90
��0
90
��0
50
240
25
�50
240
400
�85
240
Up to 24 kV
Dia. D
Dia. d
1
2
3
4
2
5
6
72
8
�2
=
3 x Cold-shrinkable
termination
assembly
Water sealing
mastic
� x Cold-shrinkable
break-out
3 x Cold-shrinkable
protection tube
� x Pulling
hook
+
Kit contentsThe complete cold-shrinkable T-ITK termination kit comprises the following components:
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable dimensions in mm.
Example:The cable is �2 kV, 3 x �50 mm2 stranded aluminium, with a diameter of 72.0 mm over outer sheath and 23.5 mm over the core insulation. The cable has an individual copper tape screen.Order a T-ITK �2-� termination kit.
All commercialised European standard
cable lugs can be used.
Cable lugs should be within the dimensions
specified (not applicable for ITK 3�2 and
ITK 324).
Orderingpart
number
VoltageUm(kV)
Diameter overcore insulation
(mm)
Diameter overouter sheath
(mm)
min. max. min. max.T-ITK �2-�
T-ITK �2-2
T-ITK 24-�
T-ITK 24-2
�2
�2
24
24
�6
26
�6
26
30
42
30
42
48
58
48
58
90
��0
90
��0
The kit also comprises a roll of adhesive
tape, flexible copper braid and installation
instructions.
+ + + T-ITK Wcold-shrinkable
termination kit
For use with copper tape screened cables.No further earthing device is necessary.
Different armour connections are
available. Please contact our
representative.
For tail lengths “X” between
500 and 700 mm.
Can be supplied with all common types of
cable lugs.
Also available with heat-shrinkable
break-out
40 mm min.
110 mm max.
46 mmmax.
X
For use with other cable types.
Please contact our representative.
�3
T-OTKTHREE CORE
OUTDOOR TERMINATIONS
Up to 24 kVApplicationThe T-OTK is a cold-shrinkable outdoor termination suited for polymeric insulated three-core cables. It will provide a necessary seal against moisture penetration and a perfect electrical field control.
Specifications and standardsThe cold-shrinkable T-OTK termination meets the requirements of CENELEC HD 629.�.
DesignCold-shrinkable termination comprising:�. Cable lugs (not included in
the standard kit). 2. Water sealing mastic.3. Silicone rubber tubes with
sheds.4. Silicone rubber tubes.5. Stress control mastic. 6. Conductive EPDM ring.7. Silicone rubber protection
tubes.8. Break-out.9. Flexible tinned copper braid
(for use with individual metal tape screened cables).
Terminationtype
VoltageUm(kV)
Diameter overcore insulation
Dia. d (mm)
Diameter overouter sheath Dia. D (mm)
Conductor sizes(for information only)
(mm2)
min. max. min. max. min. max.T-OTK �2-�
T-OTK �2-2
T-OTK 24-�
T-OTK 24-2
�2
�2
24
24
�6
26
20
26
30
42
30
42
48
58
48
58
90
��0
90
��0
50
240
50
�50
240
400
�85
240
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV
Dia. D
82
9
Dia. dT-OTK 12
T-OTK 24
2
1
3
5
4
6
2
7
�4
=
3 x Cold-shrinkable
termination assembly
Water sealing
mastic
� x Cold-shrinkable
break-out
3 x Cold-
shrinkable
protection tube
� x Pulling
hook
or
Kit contentsThe complete cold-shrinkable T-OTK termination kit comprises the following components:
Ordering instructionsSelect the part number corresponding to both the system voltage and the cable dimensions in mm.
Example:The cable is �2 kV, 3 x �50 mm2 stranded aluminium, with a diameter of 72.0 mm over outer sheath and 23.5 mm over the core insulation. The cable has an individual copper tape screen.Order a T-OTK �2-� termination kit.
All commercialised European standard
cable lugs can be used.
Cable lugs should be within the dimensions
specified.
Orderingpart
number
VoltageUm(kV)
Diameter overcore insulation
(mm)
Diameter overouter sheath
(mm)
min. max. min. max.T-OTK �2-�
T-OTK �2-2
T-OTK 24-�
T-OTK 24-2
�2
�2
24
24
�6
26
20
26
30
42
30
42
48
58
48
58
90
��0
90
��0
The kit also comprises a roll of adhesive
tape, flexible copper braid and installation
instructions.
+ + + T-OTK Wcold-shrinkable
termination kit
+
T-OTK 12 T-OTK 24
40 mm min.
110 mm max.
46 mmmax.
For use with copper tape screened cables.No further earthing device is necessary.
Different armour connections are
available. Please contact our
representative.
For tail lengths “X” between
650 and 850 mm.
Can be supplied with all common types of
cable lugs.
Also available with heat-shrinkable
break-out
X
For use with other cable types.
Please contact our representative.
�5
354550 100 100 50
50 50
Up to 17.5 kV
Bushingboottype
VoltageUm(kV)
Conductor sizes (mm2) Diameter D over termination (mm)
min. max. min. max.�5TS-NSS �7.5 max. 35 630 20 50
ClearancesThis is an unscreened boot andtherefore not save to touch when energised. When used in a metal enclosed cable box, these minimum clearances must be respected.
15TS-NSSUNIVERSAL
BUSHING BOOT
ApplicationThis universal bushing bootis manufactured from non-tracking EPDM rubber and is designed to mate with all types of cold or heat-shrinkable terminations (without sheds). The bushing part fits interface diameters between 40 and 60 mm. The system is separable and allows easy removal for testing. This boot is suitable for all angles between 90° and �80°.
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV
Kit contentsThe 3 x �5TS-NSS kit comprises3 universal bushing boots, silicone grease and installation instructions.
In mm
310
140
Dia. 90
Dia. 100
Dia. 90
Dia. 100
Dia. 65
Dia. DTermination
Additional catalogue information on power cable accessoriesis available by contacting us at the address below:
Nexans Network Solutions N.V. - Div. Euromold • Zuid III, Industrielaan �2, B-9320 ErembodegemTel.: +32 (0)53 85 02 �� • Fax: +32 (0)53 83 �0 �3 • www.nexans.com • info.euromold@nexans.com
Catalogue also available on CD-ROM
Distributed by:
0�/2
007