Post on 14-Jan-2016
description
Customer: L&T Bankura
Description qty perpnlIntermitte
nt DCload/pnl
Continuous DC
load/pnl
qty perpnl
Intermittent DC
load/pnl
Continuous DC
load/pnl
qty perpnl
Intermittent DC
load/pnl
Continuous DC
load/pnl
qty perpnl
Intermittent DC
load/pnl
Continuous DC
load/pnlClosing Coil & Tripping
coil - 1 2 400 0 2 400 0 2 400 0 0 0 0
Indicating lamps 8 0 14 9 0 15.75 8 0 14 0 0 0CRM (Aux. Plug In Type Relay) 3 4.5 0 4 6 0 5 7.5 0 0 0 0
Racking Interlock (RL2)Coil - Used in CB 1 250 5 1 250 5 1 250 5 0 0 0
Door Interlock (RL2)Coil - Used in CB 0 0 0 0 0 0 0 0 0 0 0 0
SPAJ140C 0 0 0 0 0 0 0 0 0 0 0 0PSU14/6X - Breaker
contact Multiplier relay 0 0 0 0 0 0 0 0 0 0 0 0
Anti pumping relay 1 1.5 0 1 1.5 0 1 1.5 0 0 0 0
Multi funcntion 0 0 0 0 0 0 0 0 0 0 0 0
Eight Annunciator 0 0 0 0 0 0 0 0 0 0 0 0
TCS relay 1 0 3.5 1 0 3.5 1 0 3.5 0 0 0
CV2DJ 0 0 0 0 0 0 0 0 0 0 0 0
VHXM 0 0 0 0 0 0 0 0 0 0 0 0
PQ8 0 0
REF,REM,REJ 1 13 2 26 0 1 13 0 0
RXSF1 0 0
Spring charging motor 1 350 1 350 1 350 0
PQ8 0 0 0 0 0 0 0 0 0 0 0 0
Total for each panel type (Watts) 1019 22.5 1033.5 24.25 1022 22.5 0 0Qty of Typewise panel
in (Watts) 2 2 4 4 1 1 1 1
Total DC Load(Watts) 2038 45 4134 97 1022 22.5 0 0
Total Continuous load (Watts)Total Intermitent load (Watts)
TOTAL LOAD
Total Continuous load (Watts)Total Intermitent load (Watts)
DC LOAD CALCULATIONS
7194164.5
02038 4134 102297 22.5 045
BPTIncomer MF Feeder Bus Coupler
6.6kV at IBS