28.Basics of Substations

Post on 02-Jun-2018

216 views 0 download

Transcript of 28.Basics of Substations

  • 8/11/2019 28.Basics of Substations

    1/1

    Standard clearances are:

    Voltage level Phase to Phase Phase to ground

    33kV 0.73 M 0.6 M

    132kV 3.0 M 3.1 M

    220kV 4.5 M 4.0 M

    400kV 7.0 M 6.5 M

    Minimum clearances for bare conductors or live parts of any

    apparatus in outdoor substations (Rule 64(2) (a) ii of IE rules1956)

    VOLTAGE CLASSGROUND

    CLEARANCE (M)

    SECTIONAL

    CLEARANCE

    (M)

    Not Exceeding 11kV 2.75 2.60

    Not Exceeding 33kV 3.70 2.80

    Not Exceeding 132kV 4.60 3.50

    Not Exceeding 220kV 5.50 4.30

    Not Exceeding 400kV 8.0 7.0