UNIVERSITI TEKNOLOGI MARAFAKULTI KEJURUTERAAN KIMIA
PROCESS ENGINEERING LABORATORY 1(CPE435)
No. Title Allocated Marks (%) Marks
1 Abstract/Summary 5
2 Introduction 5
3 Aims 5
4 Theory 5
5 Apparatus 56 Methodology/Procedure 10
7 Results 10
8 Calculations 10
9 Discussion 20
10 Conclusion 5
11 Recommendations 5
12 Reference / Appendix 5
13 Supervisors grading 10
TOTAL MARKS 100
Remarks:
Checked by: Rechecked by:
--------------------------- ---------------------------
Date: Dat
NAME : MUHAMMAD MUKMIN BIN ZAHARISTUDENT ID. : 2011461308GROUP : EH220 2CEXPERIMENT : REFRIGERANT UNITDATE PERFORMED : 02
THAPRIL 2012
SEMESTER : 2PROGRAMME / CODE : EH220
SUBMIT TO : CIK SITI NOR ADIEB BT IDRIS
8/10/2019 220548987 Refrigerant Unit
2/32
2
Table of content
Table of content .............................................................................................................................. 2
Abstract ........................................................................................................................................... 3
Introduction ..................................................................................................................................... 4
Aims ................................................................................................................................................ 5
Theory ............................................................................................................................................. 6
Apparatus ........................................................................................................................................ 9
Experimental procedure ................................................................................................................ 10
RESULTS ..................................................................................................................................... 12
Experiment 1.............................................................................................................................. 12
Experiment 2.............................................................................................................................. 13
Experiment 3.............................................................................................................................. 19
Experiment 4.............................................................................................................................. 23
Discussion .................................................................................................................................. 26
Conclusion .................................................................................................................................... 28
Recommendations ......................................................................................................................... 29
References ..................................................................................................................................... 30
Appendices .................................................................................................................................... 31
8/10/2019 220548987 Refrigerant Unit
3/32
3
Abstract
This experiment is carried out to study the mechanical heat pump through the operating
of the equipment SOLTEQ Mechanical Heat Pump (Model: HE165). This experiment is
conducted by doing a series of tests by manipulating the delivery temperatures and flow rates of
the cooling water. Plus, to study the mechanism of a heat pump, coefficient of performance and
heat pump performance curves. Besides, this experiment is investigating the effects of
compressor pressure ratio on the volumetric efficiency. The purpose of conducting this
experiment is to study the thermodynamics concept of energy balance and coefficient of
performance. The heat transfer is been able to determine by applying the energy balance concept.
Next, able to determine the coefficient of performance of the heat pump and how the delivery
temperatures affect the coefficient of performance. Lastly, to produce the performance curves of
the heat pump and vapour compression cycle on a p-h diagram.
8/10/2019 220548987 Refrigerant Unit
4/32
4
Introduction
In the experiment of refrigerant unit, the Mechanical Heat Pump is used to study the
vapour compression cycle. This Mechanical Heat Pump (Model: HE 165) has been designed to
provide students with a practical and quantitative demonstration of the vapour compression cycle.Refrigerators and heat pumps are both use the vapour compression cycle, and although the
applications of these machines differ, the components are essentially the same. The HE 165 is
capable of demonstrating the heat pump application where a large freely available energy source,
such as the atmosphere, is to be upgraded for water heating. The unit will be of particular interest
to those studying Mechanical Engineering, Energy Conservation, Thermodynamics, Building
Services, Chemical Engineering, Plant and Process Engineering, and Refrigeration and Air
Conditioning.
The heat pump consists of a hermetic compressor, a water cooled condenser, a
thermostatically controlled expansion valve and an air heated evaporator. The arrangements of the
components are in a manner similar to that used for many domestic air-water heat pumps where
they are visible from the front of the unit. During the operation, slightly superheated refrigerant
(R134a) vapour enters the compressor from the evaporator and its pressure is increased. Thus, the
temperature rises and the hot vapour then enters the water cooled condenser. Heat is given up to
the cooling water and the refrigerant condenses to a liquid before passing to the expansion valve.
Upon passing through the expansion valve the pressure of the liquid refrigerant is reduced.
This causes the saturation temperature to fall to below that of the atmosphere. Thus, as it flows
through the evaporator, there is a temperature difference between the refrigerant and the air being
drawn across the coils. The resulting heat transfer causes the refrigerant to boil, and upon leaving
the evaporator it has become slightly superheated vapour, ready to return to the compressor.
The temperature at which heat is delivered in the condenser is controlled by the water flow rate
and its inlet temperature. The evaporating temperature is l a r g e l y d e t e r m i n e d b y t h e
ambient conditions. However, this can be limited, either by restricting the air intake to the
evaporator, or by directing warmed air towards the intake. Instrumentations are all provided
for the measurement of flowrates of both the refrigerant and cooling water, power input to the
compressor, and all relevant temperatures.
8/10/2019 220548987 Refrigerant Unit
5/32
5
Aims
To determine the power input, heat output and coefficient of performance of a
vapour compression heat pump system
To produce the performance of heat pump over a range of source and delivery
temperatures
To plot the vapour compression cycle on the p-h diagram and compare with the
ideal cycle
To perform energy balance for the condenser and compressor
To determine the compression ratio and volumetric efficiency
8/10/2019 220548987 Refrigerant Unit
6/32
6
Theory
Refrigerators and heat pumps are devices that absorb heat at a low temperature and reject heat at a
higher temperature. Both refrigerators and heat pumps operate in the same way using a reversed
heat engine cycle, but are labeled separately according to their purpose. Devices that are used to
maintain a temperature below ambient are known as refrigerators (or air conditioners) while
devices that are used to supply heat at a higher temperature than ambient are known as heat
pumps. Some devices, in particular those used for space cooling, may be used as both a heat pump
and a refrigerator (as is the case with the Christchurch Town Hall heating/cooling system).
The vapour compression cycle is the most commonly used refrigeration/heat pump cycle and
involves the same four processes as a heat engine cycle but in the reverse order (i.e. evaporation
compression condensation expansion/throttling). Figure 1 gives a schematic representation of
the four essential mechanical components in this cycle; figure 2 shows the ideal cycle on a
pressure-enthalpy diagram.
Heat out
3 2
Condenser
Throttle Work in
Valve
Evaporator Compressor
4 1
8/10/2019 220548987 Refrigerant Unit
7/32
7
Heat in
Figure 1: Vapour Compression Cycle components
Figure 2: Ideal cycle on pressure enthalpy diagram.
In ideal vapour compression cycle the refrigerant vapour is compressed isentropically to a higher
temperature and pressure (12). The compressed vapour is then condensed isobarically which
results in heat rejection to the surroundings (23). The next step is the adiabatic throttling of the
refrigerant to the low temperature and pressure (34). The final step is where the refrigerant is
evaporated isobarically at low temperature and pressure, which results in the absorption of heat
from its surroundings (41). In an actual cycle states 1 and 3 should not lie on the saturation line
as there is subcooling (helpful to obtain state 3 in the diagram) and superheating (necessary to
avoid droplets (two phase region!) in the compressor).
The usual measure of performance of a refrigerator or heat pump is the Coefficient of Performance
COP which for a refrigerator COPRis defined as:
E
R
heat absorbed at the lower temperatureCOP
compressor net work
Q
W= = (1a)
3 2
4 1
Superheating
SubcoolingCritical Point
Liquid
Pressure
Enthalpy
8/10/2019 220548987 Refrigerant Unit
8/32
8
For a heat pump COPH:
C
H
heat rejected at the higher temperatureCOP
compressor net work
Q
W= = (1b)
where E, C, R, H stand for Evaporator, Compressor, Refrigeration, and Heat pump respectively.
Note: The cooling water and refrigerant flow rate displays is in percentage (%). Below are the
formula to convert cooling water and refrigerant flow rate to LPM
() ()
() ()
8/10/2019 220548987 Refrigerant Unit
9/32
9
Apparatus
SOLTEQ Mechanical Heat Pump Model: HE165
8/10/2019 220548987 Refrigerant Unit
10/32
10
Experimental procedure
General Start-up Procedure
1. The unit and all instruments are checked in proper condition.
2. Both water source and drain are checked connected then the water supply is open and
the cooling water flow rate is set at 1.0LPM.
3. The drain hose at the condensate collector is checked connected.
4. Power supply is connected and the main power is switched followed by main switch
at the control panel.
5. The refrigerant compressor is switched on. As soon as temperature and pressure were
constant, the unit was ready for experiment.
General Shut-down Procedure
1. The compressor is switched off, followed by main switch and power supply.
2. The water supply is closed and water is ensured not left running.
Experiment 1: Determination of power input, heat output and coefficient of performance
Objective:
To determine the power input, heat output and coefficient of performance of a vapour
compression heat pump system
Procedures:
1. The general start-up procedures are performed.
2. The cooling water flow rate is adjusted to 40%.
3. The system is allowed to rub for 15 minutes.
4. All necessary reading is recorded into experimental data sheet.
Experiment 2: Production of heat pump performance curves over a range of source and
delivery temperaturesObjective:
To produce the performance of heat pump over a range of source and delivery
temperatures
Procedures:
1. The general start-up procedures are performed
8/10/2019 220548987 Refrigerant Unit
11/32
11
2. The cooling water flow rate is adjusted to 80%.
3. The system is allowed to run for 15 minutes.
4. All necessary readings are recorded into the experimental data sheet.
5. The experiment with reducing flow rate is repeated so that the cooling water
outlet temperature increases by about 3(40% and 60%).
6. The experiment might be repeated at different ambient temperature.
Experiment 3: Production of water vapour compression cycle on p-h diagram and energy
balance study
Objective:
1. To plot the vapour compression cycle on the p-h diagram and compare with the ideal
cycle
2. To perform energy balances for the condenser and compressor
Procedures:
1. The general start-up procedures are performed
2. The cooling water flow rate is adjusted to 40% and the system is allowed to run for
15 minutes.
3. All necessary readings are recorded into experimental data sheet.
Experiment 4: Estimation of effect of compressor pressure ratio on volumetric efficiency
Objective:
To determine the compression ratio and volumetric efficiency
Procedures:
1. The general start-up procedures are performed.
2. The cooling water flow rate is adjusted to 40%.
3. The system is allowed to run for 15 minutes.
4. All necessary readings are recorded into experimental data sheet.5. The experiment might be repeated at different compressor delivery pressure.
8/10/2019 220548987 Refrigerant Unit
12/32
12
RESULTS
Experiment 1Cooling water flow rate, FT 1 % 40.0
Cooling water inlet temperature, TT 5 C 28.8
Cooling water outlet temperature, TT 6 C 30.0
Compressor power input W 162
For reading 1,
Cooling water flow rate, LPM = ()
x 5 LPM
=
= 2.0 LPM
x
x
= 3.333 x 10
-5m
3/s
Find h5and from table saturated water-temperature using interpolation
T (C) h (kJ/kg)
25 104.83
28.8 120.72
30 125.74
From saturated table, h6= 125.74
h5= 120.72 kJ/kg h6= 125.74 kJ/kg water= 1000kg/m3
Mass flow rate =
x
= 0.0333 kg/s
Ein = Eout
Mh5 = QH+ mh6
QH = m(h5h6)
= 0.0333 kg/s (120.72 125.74) kJ/kg
8/10/2019 220548987 Refrigerant Unit
13/32
13
= -0.167 kJ/s
COPH =
=
= 0.00103
Experiment 2
Reading 1 Reading 2 Reading 3
Cooling water flow rate, FT 1 % 60.0 40.0 20.0
Cooling water inlet temperature, TT
5
C 28.7 28.8 28.6
Cooling water outlet temperature,
TT 6
C 29.7 30.0 31.2
Compressor power input W 160 162 160
8/10/2019 220548987 Refrigerant Unit
14/32
14
Reading 1,
Cooling water flow rate, LPM = ()
x 5 LPM
=
= 3.0 LPM
x
x
= 5 x 10-5m3/s
Find h5and h6from table saturated water-temperature using interpolation.
T (C) h (kJ/kg)
25 104.83
28.7 120.30
30 125.74
T (C) h (kJ/kg)
30 125.74
29.7 124.49
35 146.64
h5=120.30kJ/kg
h6= 124.49 kJ/kg
water= 1000kg/m3
Mass flow rate =
x
= 0.05 kg/s
Ein = Eout
mh5 = QH+ mh6
QH = m(h5h6)
= 0.05 kg/s (120.30124.49) kJ/kg
= -0.2095 kJ/s
8/10/2019 220548987 Refrigerant Unit
15/32
15
COPH =
=
= 0.0013
Reading 2,
Cooling water flow rate, LPM = ()
x 5 LPM
=
= 2.0 LPM
x
x
= 3.333 x 10
-5m
3/s
Find hB2,1and hB2,2from table saturated water-temperature using interpolation.
T (C) h (kJ/kg)25.0 104.83
28.8 120.72
30.0 125.74
From saturated table, h6= 125.74
h5= 120.72 kJ/kg h6= 125.74 kJ/kg water= 1000kg/m3
Mass flow rate =
x
= 0.0333 kg/s
Ein = Eout
mh5 = QH+ mh6
QH = m(h5h6)
= 0.0333 kg/s (120.72 125.74) kJ/kg
= -0.167 kJ/s
COPH =
=
= 0.00103
8/10/2019 220548987 Refrigerant Unit
16/32
16
Reading 3,
Cooling water flow rate, LPM = ()
x 5 LPM
=
= 1.0 LPM
x
x
= 1.667 x 10
-5m
3/s
Find hB3,1and hB3,2from table saturated water-temperature.
T (C) h (kJ/kg)
25.0 104.83
28.6 119.88
30.0 125.74
T (C) h (kJ/kg)
30.0 125.74
31.2 130.76
35.0 146.64
h5= 119.88 kJ/kg h6 = 130.76 kJ/kg water= 1000kg/m3
Mass flow rate =
x
= 0.01667 kg/s
Ein = Eout
Mh5 = QH+ mh6
QH = m(h5h6)
= 0.01667 kg/s (119.88 130.76) kJ/kg
= -0.181 kJ/s
COPH =
=
= 0.0011
8/10/2019 220548987 Refrigerant Unit
17/32
17
From the value that calculated, graph can be constructed
T6(C) Power
input(kJ/s)
Qh(kJ/s) COP
Reading 1 29.7 160 0.2095 0.0013
Reading 2 30.0 162 0.167 0.004268
Reading 3 31.2 160 0.181 0.0011
Graph 1
30.3, 0.004627
31.1, 0.004268
32.5,0.003797
0
0.0005
0.001
0.0015
0.002
0.0025
0.003
0.0035
0.004
0.0045
0.005
30 30.5 31 31.5 32 32.5 33
COP
Temperature (C)
graph of COP vs temperature
8/10/2019 220548987 Refrigerant Unit
18/32
18
Graph 2
Graph 3
30.3, 0.8931
31.1, 0.8365
32.5, 0.7519
0.74
0.76
0.78
0.8
0.82
0.84
0.86
0.88
0.9
0.92
30 30.5 31 31.5 32 32.5 33
Heattransfer,QH(kJ/s)
Temperature(C)
graph of QH vs temperature
30.3, 193
31.1, 196
32.5, 198
192
193
194
195
196
197
198
199
30 30.5 31 31.5 32 32.5 33
p
ower(kJ/s)
Temperature (C)
graph of power input vs temperature
8/10/2019 220548987 Refrigerant Unit
19/32
19
Experiment 3
Refrigerant flow rate, FT2 % 35.2
Refrigerant pressure (low), P1 Bar (abs) 3.1
Refrigerant pressure (high), P2 Bar (abs) 8.0
Refrigerant temperature, TT1 C 5.9
Refrigerant temperature, TT2 C 34.2
Refrigerant temperature, TT3 C 31.3
Refrigerant temperature, TT4 C 20.4
Cooling water flow rate, FT1 % 40.0
Cooling water inlet temperature, TT5 C 27.0
Cooling water outlet temperature ,
TT6
C 32.4
Compressor power input W 182
Find hc1and hc2using interpolation from superheated R-134a table
At T = 5.9 C
p (MPa) h (kJ/kg)
0.28 256.05
0.31 255.26
0.32 254.99
At T = 34.2 C
p (MPa) h (kJ/kg)
0.80 270.34
8/10/2019 220548987 Refrigerant Unit
20/32
20
Find hc3and hc4from saturated R-134a table at given T and P = 0.8MPa
T (C) h (kJ/kg)
31.3 267.29
20.4 95.47
h1= 255.26 kJ/kg
h2= 270.99kJ/kg
h3= 267.29/kg
h4 = 95.47kJ/kg
Condenser energy balance
Refrigerant flow rate, LPM = ()
x 1.26 LPM
=
= 0.44 LPM
x
x
= 7.333 x 10
-6m
3/s
Mass flow rate =
x
= 0.00733kg/s
Ein = Eout
QH =
QH = ( )
=0.00733 kg/s (267.29 95.47) kJ/kg
= 1.259kJ/s
Compressor energy balance
( )
( )
8/10/2019 220548987 Refrigerant Unit
21/32
21
From the value that calculated, p-h diagram can be constructed
h
(kJ/kg)
Pressure
(Mpa)
255.26 0.31
270.99 0.8
267.29 0.8
95.47 0.8
Graph 1
Experimental graph
255.26, 0.31
270.29, 0.8267.29, 0.895.47, 0.8
95.47, 0.31
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0 50 100 150 200 250 300
Pressure(MPa)
Enthalphy,h (KJ/Kg)
graph of pressure vs enthalphy
8/10/2019 220548987 Refrigerant Unit
22/32
22
Theoretical graph
8/10/2019 220548987 Refrigerant Unit
23/32
23
Experiment 4
Refrigerant flow rate , FT2 % 36.0 35.5
Refrigerant pressure (low) , P1 Bar (abs) 3.2 3.1
Refrigerant pressure (high) , P2 Bar (abs) 8.1 8.1
Refrigerant temperature ,TT1 C 6.4 6.1
Reading 1
Compressor pressure ratio =
=
= 0.3951
Volumetric efficiency =
Refrigerant flow rate, LPM = ()
x 1.26 LPM
= 0.36 x 1.26 LPM
= 0.4536 LPM
Change LPM to the kg/s
Mass flow rate = 0.4536 LPM x
x
()x
x 4.25
8/10/2019 220548987 Refrigerant Unit
24/32
24
= 3.213 x 10-5
Density of refrigerant 134a = 4.25
Actual volume flow rate =
= 3.213 x 10-5
x
= 7.56. x 10-6
Volumetric efficiency =
= 7.56. x 10-6
x
= 0.4696
Reading 2
Compressor pressure ratio =
=
= 0.3827
Volumetric efficiency =
Refrigerant flow rate, LPM = ()
x 1.26 LPM
= 0.355 x 1.26 LPM
= 0.4473 LPM
Change LPM to the kg/s
8/10/2019 220548987 Refrigerant Unit
25/32
25
Mass flow rate = 0.4473 LPM x
x
()x
x 4.25
= 3.168 x 10-5
Density of refrigerant 134a = 4.25
Actual volume flow rate =
= 3.213 x 10-5
x
= 7.454x 10-6
Volumetric efficiency =
= 7.454 x 10-6
x
= 0.4627
Time Min 15 20
Refrigerant flow rate , FT2 % 36.0 35.5
Refrigerant pressure (low) , P1 Bar (abs) 3.2 3.1
Refrigerant pressure (high) , P2 Bar (abs) 8.1 8.1
Refrigerant temperature ,TT1 C 6.4 6.1
Compressor pressure ratio - 0.3951 0.3827
Volumetric efficiency - 0.4696 0.4627
8/10/2019 220548987 Refrigerant Unit
26/32
26
Discussion
This experiment was carried out to calculate the performance each of the equipment in
the refrigerant unit. In the first experiment, the power input of the heat pump was recorded at162kJ/s in order to absorb 0.167kJ/s heat from the surroundings. The value of enthalpy at given
temperature was calculated using the interpolation method based on the value at Table A-4. The
value obtain was used to calculate the amount rate heat transfer in the system. The coefficient of
performance of the heat pump used is 0.00103.
For the second experiment, the same step as the first experiment was repeated at different
cooling water flow rate which is at 60%, 40% and 20%. From the experiment, the power input
for the heat pump is different for each water flow rate, which are, 160kJ/s, 162kJ/s and 160kJ/s
respectively. The power input varies as the cooling water flow rate decreases. The same method
was used to calculate the rate of heat transfer and the coefficient of performance (COP) for the
heat pump. The COP calculated for cooling water flow rate at 60%, 40% and 20% is 0.0013,
0.00103 and 0.0011 respectively. The COP of heat pump decreases as the cooling water flow rate
decreases.
In the third experiment, the change in pressure and temperature for refrigerant R-134A
after passing condenser and compressor was recorded. The enthalpy was calculated using
interpolation to calculate the change of enthalpy at compressor and condenser. At the compressor
the superheated refrigerant was compressed from 0.31 MPa at 5.9C to 0.8Mpa at 34.2 C and
the enthalpy calculated is 255.26kJ/kg and 270.99kJ/kg respectively. The R-134A enters the
compressor superheated then compressed at constant entropy the leaves as superheated. The
refrigerant then enter the condenser at temperature of 31.3C at 0.8MPa and leave the condenser
at temperature at 20.4C at 0.8MPa. The pressure is constant because the condenser undergoes
the heat rejection process at constant pressure. The enthalpy calculated at 31.3C and 20.4C is
267.29/kg and 95.47kJ/kg respectively. The enthalpy was decreased because at the condenser,
the heat energy is released to surrounding cause the heat energy in the refrigerant to drop.
8/10/2019 220548987 Refrigerant Unit
27/32
27
Last experiment, the compression ratio and volumetric efficiency are been calculated.
The systems are allowed to run at different period of time before the readings were taken. First,
the systems are allowed to run for 15 minute then the steps repeated for 20 minute period.
The values of compressor pressure ratio are 0.3951 and 0.3827 respectively. There is slightly
difference in the ratio calculated. This is due to the difference in the reading of pressure before
entering the compressor. However, the pressure leaving the compressor for both period of time is
the same which is 0.81MPa. The volumetric efficiencies are then calculated, and the values are
0.4696 and 0.4627 respectively. There is also slightly difference in the value calculated that is
due to the difference in the refrigerant flow rate.
Higher compression ratio allows an engine to extract more mechanical energy from a
given mass of air fuel mixture due to its higher thermal efficiency and is most wanted. Based on
the value of volumetric efficiency, we can compare the actual value of volumetric flow rate in
theory to the value that obtained from this experiment. The differences of both values are high.
A several steps might be conducted inaccurately which results in all experiments in such an
outrageous values. Firstly the water flow rate is not in stable condition while taking reading.
Reading is been taken in the range +6 from the actual reading. Next experiment shows that the
flow rate of water that we should take is 60% but the reading is not constant. Hence, the reading
is been taken when it reach 60% and does not increase exceed 60%. This happen because the
water source in laboratory is not enough for this apparatus and the present of pump.
As going through this experiment, time does not give much effect, but a little time
difference could make a little variance from the theory
8/10/2019 220548987 Refrigerant Unit
28/32
28
Conclusion
Overall this experiment is considering success. First and foremost experiment, the power
input, heat output and coefficient of performance of a vapour compression heat pump system are
been determined. In experiment 1, the values QH and COPH are- 0.167kJ/s and 0.00103. For
second experiment, the performances of heat pump over a range of source and delivery
temperature are been able to produce. The values of COPH are 0.0013, 0.00103, and 0.0011. The
values are decreasing. From the results, it can be concluded that the heat pump functioning with
a high percent of flow rate have higher efficiency compare to the lower flow rate. As show in
experiment 3, the p-h diagram of vapour compression cycle is been plotted successfully and able
to be compared with the ideal cycle and able to perform energy balances for the condenser and
compressor. It clearly can be seen that the values are differ in small amount. Last experiment,
ratio and volumetric efficiency are been able to be calculated. The ratio is 0.3951 and 0.3827 and
for the volumetric efficiency is 0.4696 and 0.4627. There is slightly difference due to difference
in pressure and refrigerant flow rate.
8/10/2019 220548987 Refrigerant Unit
29/32
29
Recommendations
1. Consultation is compulsory in order to make sure the experiments are conducted
properly.
2. To make sure that the machine in good conditions and the experiment are been doing
wrong, we have to understand the general start up and general shut down.
3. Before the experiment begin, ensure that the mechanical heat pump should run and warm
up early for 15 minutes. It should be notice that, surrounding in the laboratory also affect
the result, thus it hard to get an accurate reading.
4. A trial should not be forgotten before running the experiment. This is due to get an
accurate result in experiment 3. Thus, the graph of vapour compression cycle plotted on
p-h diagram of R-134a is in correct order with appropriate ideal cycle.
5. While running the experiment, if some technical problems occur directly ask the
technician to overcome the problems.
8/10/2019 220548987 Refrigerant Unit
30/32
30
References
UiTM Faculty of Chemical Engineering, Laboratory Manual CHE 465, Chemical
Engineering Lab 1
www.tyxer.hubpages.com/hub/theory-of-refrigeration
www.solution.com.my/pdf/HE165(A4).pdf
www.1.eere.energy.gov/manufacturing/tech_deployment/pdf/heatpump.pdf
Yunus A. Cengel, Micheal A. Boles Thermodynamics An Engineering Approach , McGraw-Hill
Book Company, 7th
edition 2011.
http://www.tyxer.hubpages.com/hub/theory-of-refrigerationhttp://www.tyxer.hubpages.com/hub/theory-of-refrigerationhttp://www.solution.com.my/pdf/HE165(A4).pdfhttp://www.solution.com.my/pdf/HE165(A4).pdfhttp://www.1.eere.energy.gov/manufacturing/tech_deployment/pdf/heatpump.pdfhttp://www.1.eere.energy.gov/manufacturing/tech_deployment/pdf/heatpump.pdfhttp://www.1.eere.energy.gov/manufacturing/tech_deployment/pdf/heatpump.pdfhttp://www.solution.com.my/pdf/HE165(A4).pdfhttp://www.tyxer.hubpages.com/hub/theory-of-refrigeration8/10/2019 220548987 Refrigerant Unit
31/32
31
Appendices
Figure 1: Compressor
Figure 2: Condenser
8/10/2019 220548987 Refrigerant Unit
32/32
Figure 3: R-134A
Figure 4: Evaporator