Stress Strain Test and Fittings Tensile Test
NEETRAC Project Number: 06-086
November, 2006
Requested by: Dr. Colin McCullough 3M
Principal Investigator: Paul Springer, PE
Reviewed by: Dale Callaway
A Research Center of the Georgia Institute of Technology
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 2 of 12
1033 ACCR Conductor Stress Strain Test and Fittings Tensile Test
NEETRAC Project Number: 06-086
November, 2006
Summary Three AFL dead ends were tested to confirm holding strength exceeds 95% of nominal RBS required by ANSI C119.4. All samples exceeded nominal RBS. Stress-strain tests in accordance with the Aluminum Association’s 1999 guide characterized the elastic and short-term creep properties for 3M 1033 ACCR conductor. Samples
1) Three (3) ACA compression dead ends compressed on 21-foot sections of 1033 ACSR conductor. Connector installation was performed by ACA Conductor Accessories in Spartanburg, South Carolina.
2) Reel of 1033 ACCR conductor for stress-strain tests.
Procedure
I) Connector tensile tests (three dead-ends): Bird caging (excess slack) from the compression operation was worked to the conductor free end. Cast-resin fittings were then installed in accordance with a procedure developed for lab testing of ACCR conductors. Samples were loaded into an MTS tensile machine and pulled to destruction at a rate of 17,000 lbs/min.
II) Stress-strain: Samples were taken from near the center of the reel to ensure properties
are representative of the “as-manufactured” conductor. Bolted clamps were installed on both sides of each cut to prevent any component from shifting. Cast-resin terminations were applied to the sample ends using a procedure designed to preserve the conductor manufacturing pre-stress, and therefore ensure that test samples behave as similar as practical to in-service conductor.
The 1999 Aluminum Association guide for conductor stress-strain testing was followed with one exception: values for the elastic properties of the metal matrix composite (MMC) core were used instead of values provided in the guide. The elastic coefficients in the guide apply to steel core, and therefore are non-applicable for MMC conductor core strands.
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 3 of 12
Results
Tensile Tests:
Three (3) dead end connectors were pulled to destruction. The stress-strain composite sample was pulled to destruction following the stress strain test. The core sample was tensile tested, but results were not representative because a strand failure occurred at a location damaged during removal of the aluminum strands. Figure 3 shows the tension and actuator displacement data from the tensile machine. The 3M data sheet for 1033 ACCR lists nominal RBS as 35,470 lb.
The following breaking loads were recorded:
Sample # Breaking Load % RBS Failure Mode (lb)
Dead End1: 36,030 102 All strands mid span Dead End2: 36,160 102 Most strands ~2 feet from dead end Dead End3: 37,070 105 Most strands mid span Stress-strain conductor: 36,120 102 All strands mid-span
Figure 1, dead
end sample pre-test Figure 2, typical mid-span break
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 4 of 12
1033 kcmil, Type 13, 3M Composite ConductorTensile Test Data
0
5000
10000
15000
20000
25000
30000
35000
40000
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0Crosshead Position (inches)
Load
(lb)
Dead End 1
Dead End 2
Dead End 3
Stress-Strain Composite
RBS
95% RBS Acceptance Criterion
Figure 3, dead end tensile test results
Stress-strain: Detailed Procedure:
Composite conductor (RBS 35,470 lbs):
1) Apply load of 1,000 lbs. Remove sag with a mid-span support 2) Install extensometer, and set to zero. 3) Pull to 30% of RBS (10,641 lbs)* 4) Hold for 30 minutes. 5) Relax load to 1,000 lbs. 6) Pull to 50% RBS (17,740 lbs) 7) Hold for one hour 8) Relax load to 1,000 lb 9) Pull to 70% RBS (24,830 lb) 10) Hold for one hour. 11) Relax load to 1,000 lbs. 12) Pull to 75% RBS (26,600 lbs). 13) Relax load to 1,000 lbs, and remove the extensometer (for its own protection). 14) Pull sample to destruction at 17,000 lbs/min. *Due to a human error, sample was pulled to only 25% RBS, or 8,870 lb. See “Conclusions” for discussion of affect on overall accuracy for the test.
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 5 of 12
Core strands (nominal rating is 19,183 lbs):
1) Pull to calculated initial tension (in this case, 300 lbs). Remove sag with a mid-span support
2) Install extensometer, and set to zero 3) Pull to same strain as conductor at start of 30% of RBS test (0.0927%) 4) Hold for 30 minutes. 5) Relax load to 300 lbs. 6) Pull to same strain as conductor at start of 50% of RBS test (0.2041%) 7) Hold for one hour. 8) Relax load to 300 lbs. 9) Pull to same strain as conductor at start of 70% of RBS test (0.3159%) 10) Hold for one hour 11) Relax load to 300 lbs. 12) Pull to 75% of the core rating (14,390 lbs) 13) Relax load to 300 lbs, and remove the extensometer (for its own protection). 14) Pull sample to destruction at 10,000 lbs/min.
Figure 4, Composite stress-strain Figure 5, core stress-strain performed to same strains as composite sample
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 6 of 12
1033 kcmil, Type 13, 3M Composite ConductorStress-Strain Data
0
5000
10000
15000
20000
25000
30000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Figure 6, plot of raw data recorded during conductor stress-strain test
1033 kcmil, Type 13, 3M Composite ConductorCore Stress-Strain Data
0
20000
40000
60000
80000
100000
120000
140000
160000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Figure 7, plot of raw data recorded during core stress-strain test
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 7 of 12
1033 kcmil, Type 13, 3M Composite ConductorStress-Strain Data
y = 113497x - 12644R2 = 0.9999
y = -63454x2 + 97728x + 1040.5R2 = 0.9999
0
5000
10000
15000
20000
25000
30000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Stress-strain data
Initial modulus data
Final modulus data
Linear (Final modulus data)
Poly. (Initial modulus data)
Figure 8, construction of conductor initial and final moduli on stress-strain data
1033 kcmil, Type 13, 3M Composite ConductorStress-Strain Initial and Final Modulus Data, Shifted on Strain Axis for Zero Intercept
y = 112618x - 13149R2 = 0.9998
y = -63455x2 + 99070xR2 = 0.9999
0
5000
10000
15000
20000
25000
30000
35000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Translated initial modulus data
Translated final modulus data
Linear (Translated final modulus data)
Poly. (Translated initial modulus data)
Figure 9, conductor stress-strain data translated along strain axis for correct zero intercept
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 8 of 12
1033 kcmil, Type 13, 3M Composite ConductorCore Stress-Strain Data with Construction of Initial and Final Modulus
y = 329782x - 2541
y = -62411x2 + 334453x + 3311.8
0
20000
40000
60000
80000
100000
120000
140000
160000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Core Stress-strain data
Final Modulus Selected Data
Initial Modulus Data
Linear (Final Modulus Selected Data)
Poly. (Initial Modulus Data)
Figure 10, construction of core moduli on stress-strain data
1033 kcmil, Type 13, 3M Composite Conductor Core Translated Moduli
y = -62412x2 + 335687xR2 = 0.9999
y = 329782x - 5800.6
0
20000
40000
60000
80000
100000
120000
140000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
Strain (%)
Stre
ss (p
si)
Translated Initial ModulusTranslated Final ModulusPoly. (Translated Initial Modulus)Linear (Translated Final Modulus)
Figure 11, core moduli, data translated along strain axis for correct zero intercept
National Electric Energy Testing, Research & Applications Center
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 9 of 12
1033 kcmil, Type 13 ACCR 3M Composite Conductor, Combined Stress-Strain Diagram
Initial Aluminum y = -56440x2 + 61339xFinal Aluminum y = 77129x - 12730
Initial Composite y = -63455x2 + 99070x
Initial Core y = -7015.1x2 + 37731xFinal Core y = 37067x - 649.34
Final Composite y = 112618x - 12818
0
5000
10000
15000
20000
25000
30000
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40Strain (%)
Stre
ss*a
rea
ratio
Initial Composite Final Composite
Initial Core Final Core
Initial Aluminum Final Aluminum
Figure 12, combined stress-strain graph (see following text for equations)
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 10 of 12
Equations for Stress-Strain Properties. Coefficients below are with respect to actual area. Figure 10 contains the equations normalized for area ratio of core and aluminum constituents): Composite Conductor Properties, direct test values: “Initial” Modulus for Stress Strain Curve: Stress (psi) = -63454*(Strain%)2 + 97728*(Strain%) + 1040.5 Final Modulus for Stress Strain Curve: Stress (psi) = 113497*(Strain%) - 12644 Tensile Test, Stress Strain Sample: 36120 lb (102% RBS) Composite Conductor, data shifted along strain axis to provide correct zero strain reference: “Initial” Modulus for Stress Strain Curve: Stress (psi) = -63455*(Strain%)2 + 99070*(Strain%) Final Modulus for Stress Strain Curve: Stress (psi) = 112618*(Strain%) – 13149 Core Strand Properties, direct test values: “Initial” Modulus for Stress Strain Curve: Stress (psi) = -62411*(Strain%)2 + 334453*(Strain%) + 3311.8 Final Modulus for Stress Strain Curve: Stress (psi) = 329782*(Strain%) – 2541 Core Properties, data shifted along strain axis to provide correct zero strain reference: “Initial Modulus” for Stress Strain Curve: Stress (psi) = 62412*(Strain%)2 + 335687*(Strain%) Final Modulus for Stress Strain Curve: Stress (psi) = 399782*(Strain%) – 5801 Aluminum Properties (computed, direct measurement is not possible): “Initial” Modulus for Stress Strain Curve: Stress (psi) = -63587*(Strain%)2 + 69107*Strain Final Modulus for Stress Strain Curve: Stress (psi) = 86896*Strain - 14342
CONCLUSION: The three dead end samples exceeded the ANSI C119.4 strength requirement of 95% RBS. Stress-strain data are provided to support transmission line design programs. The error in setting the load for the 30% load hold was evaluated and resolved in accordance with NEETRAC’s quality management system. The discrepancy was discussed with technical staff at 3M. It was concluded that the 5% change in tension did not significantly change the creep that occurred during the 30 minute load period. It was also observed that creep during the hour at 50% RBS, and during the hour at 70% RBS were both at the correct load. Most of the conductor creep missing from the 30% load hold period would be recovered during two hours at significantly higher loads. Therefore the change in the shape of the initial modulus curve due to the experimental error is small relative to other accepted experimental errors. A mutual decision was reached to accept the test results as representative of the conductor behavior. Figure 11 shows the actual load profile along with the correct target loads.
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 11 of 12
1033 kcmil, Type 13, 3M Composite ConductorLoad vs. Time
0
5000
10000
15000
20000
25000
30000
35000
40000
0 30 60 90 120 150 180 210
Elapsed Time (minutes)
Load
(lbs
)
Tension
RBS
75% RBS
70% RBS
50% RBS
30% RBS
Figure 13, recorded load data and target loads for composite stress-strain test EQUIPMENT LISTING
1) MTS Servo-hydraulic tensile machine, Control # CQ 0195 (load and crosshead data) 2) Dynamics Research Corporation (DRC)/NEETRAC cable extensometer, Control # CQ 3002
(strain data). 3) Yokogawa DC100 data acquisition system, Control # CN 3022 (temperature data) 4) HBM linear position indicator for crosshead displacement (for reference only)
REFERENCES AND STANDARDS LISTING
1) ASTM E4, (Calibration of Load Testing Machines) 2) ANSI C119.4, (Connector testing) 3) Aluminum Association Guide for Stress-Strain Testing, 1999
1033 ACCR, Dead End Tensile and Conductor Stress-Strain NEETRAC Project Number 06-086 Page 12 of 12
DISCLAIMER TECHNICAL INFORMATION AND DATA; PRODUCT USE. Technical information and data, recommendations, and other statements provided by 3M are based on information, tests, or experience which 3M believes to be reliable, but the accuracy or completeness of such information is not guaranteed. Some of the standard industry tests conducted by 3M were originally designed for conventional conductors and were adapted by 3M for use with composite conductors; references to such tests should be considered in light of this fact. Such technical information and data are intended for persons with knowledge and technical skills sufficient to assess and apply their own informed judgment to the information. No license under any 3M or third party intellectual property rights is granted or implied with this information. Buyer is responsible for evaluating and determining whether the 3M product is suitable and appropriate for Buyer’s particular use and intended application. The conditions of evaluation, selection, and use of a 3M product can vary widely and affect the use and intended application of a 3M product. Because many of these conditions are uniquely within Buyer’s knowledge and control, Buyer must evaluate and determine whether the 3M product is suitable and appropriate for a particular use and intended application. 3M products are sold or provided to Buyer solely for Buyer’s internal manufacturing use or consumption and may not be repackaged, resold, or redistributed in any manner without the prior written consent of 3M. WARRANTY AND LIMITED REMEDY. Unless stated otherwise in 3M’s product literature, packaging inserts or product packaging for individual products, 3M warrants that each 3M product meets the applicable specifications at the time 3M ships the product. Individual products may have additional or different warranties as stated on product literature, package inserts or product packages. 3M MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR ANY IMPLIED WARRANTY ARISING OUT OF A COURSE OF DEALING, CUSTOM OR USAGE OF TRADE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user’s application. If the 3M product is defective within the warranty period, your exclusive remedy and 3M’s and seller’s sole obligation will be, at 3M’s option, to repair the product, replace the product, or refund the purchase price. LIMITATION OF LIABILITY. Except where prohibited by law, 3M and seller will not be liable for any loss or damage arising from the 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.